PULSE TRAIN INPUT—A500(L)
5.4 Pulse Train Input Parameter List
*1 Indicates the frequency division ratio for the input pulses. The frequency resolution to the input pulses varies with
the setting.
Parameter Number
Name
Setting Range
Minimum
Increments
Factory Setting
384 (*1)
Input pulse frequency division ratio
0 to 250
1
0
385
Zero-input pulse frequency
0 to 400Hz
0.01Hz
0
386
Maximum-input pulse frequency
0 to 400Hz
0.01Hz
60
CAUTION
When the Pr. 384 value is "0" (factory setting), Pr. 385 and Pr. 386 do not function even if their
values have been set.
Note that if you set any value other than 0Hz in Pr. 385, m erely turning on the start signal w ill
start the m otor at the preset frequency w ithout a pulse train input com m and.