ORIENTATION CONTROL AT A MACHINE END— V500
3) External stop position command (Pr. 350="2")
Mount the option FR-A5AX and set a stop position using 12-bit data (binary input).
•The value set in Pr. 360 "external position command selection" should be the number of stop
positions less 1.
Pr. 360 Setting
Description
0
Speed command is made invalid (speed command with the FR-A5AX)
1
Set 4096 stop positions at regular intervals
2 to 127
Set the stop position command dividing up to 128 stop positions at regular intervals. If the
external stop command entered is greater than the setting, the stop positions are the same as
those in the maximum external stop command value.
<Example>
When the number of stop positions is 90 (divided at intervals of 4 degrees), 90 - 1 = 89. Hence, set "89".
[Example 1] 4 stop positions
[Example 2] 8 stop positions
[Example 3] 120 stop positions
Pr. 360 = "3"
Pr. 360 = "7"
Pr. 360 = "119"
180°
(2)
90°
(1)
CW
Origin (0)
270°
(3 or more)
315°
(6)270°
(5)225°
45°(1)
135°(3)
180°(4)
90°(2)
Origin (0)
(7 or more)
CW
Origin (0)
At intervals
of 3
°
70
°
90)
180
°
(60)
90
°
(30)
CW
At intervals
of 3
°