Item
Specifications
Standard
EMC: EN-61326-1: 2013
UL: UL61010-1
LVD: EN-61010-1: 2010
Usage
environment
Operating temperature
-5 - +55°C (Daily average temperature is 35°C or lower)
Operating humidity
30 - 85%RH (No condensation)
Storage temperature
-10 - +60°C
Operating altitude
2000m or below
Commercial frequency withstand voltage
b/w all terminals (except for communication circuit and frame GND terminal) and casing:
2000V AC, 1min
b/w all terminals of current input, voltage input / auxiliary power : 2000V AC, 1min
b/w all terminals of current input, voltage input, auxiliary power and all terminals of digital / pulse
input, pulse / alarm output, communication: 2000V AC, 1min
Insulation resistance
10M
Ω
or more at the same part above (500V DC)
Appropriate
wire
Terminals of auxiliary
power circuit and voltage
input
stranded wire: AWG26-14(0.13
~
2.0mm
2
)
single wire
: AWG26-14(
φ
0.41
~
1.62mm)
Terminals of current input
stranded wire: AWG18-14(0.82
~
2.0mm
2
) *4
single wire
: AWG18-14(
φ
1.03
~
1.62mm)
Terminals of input/output
stranded wire: AWG22-14(0.33
~
2.0mm
2
)
single wire
: AWG22-14(
φ
0.65
~
1.62mm)
Tightening
torque
Screws for terminals of
auxiliary power circuit and
voltage input
0.8 - 1.0N
・
m
Screws for terminals of
current input and
input/output
0.5 - 0.6N
・
m
Screws for installation to
the panel
0.63N
・
m
Mass
0.3kg
External dimensions (unit: mm)
75 (W) x 90 (H) x 75 (D) (expect for the protruding portions)
(Maximum dimension including the protruding portions: 79 (W) x 90 (H) x 75 (D))
Product life expectancy
10 years (under usage environmental condition indicated above)
Possible combination optional unit for UL
EMU4-LM, EMU4-CM-C, EMU4-CM-CIFB, EMU4-CM-MT
*1: 110V, 220V, 440V AC can connected to this unit directly. For the circuit over this voltage, transformer (VT) is necessary (Primary voltage of VT
can be set up to 6600V, and secondary voltage of VT can be set up to220V as optional setting).Star- delta connection and delta-star connection
transformer of cannot measure definitely to be out of phase. Please use a transformer of the same connection.
*2: 63.5/110V – 277/480V AC can connected to this unit directly. For the circuit over this voltage, transformer (VT) is necessary (Primary voltage of
VT can be set up to 6600V, and secondary voltage of VT can be set up to220V as optional setting).Star- delta connection and delta-star
connection transformer of cannot measure definitely to be out of phase. Please use a transformer of the same connection.
*3: Accuracy of A, V, W, var, VA, PF, Hz, HI and HV is specified according to the maximum scale value at standard test condition. (Maximum scale
values lists below.)
A,HI
V,HV
W, var, VA
PF
Hz
5A
1P2W:600V
1P3W:300V
3P3W:600V
3P4W:600V
1P2W: 2000W (440V
×
5A
×
1=2200W
→
2000)
1P3W: 1000W (110V
×
5A
×
2=1100W
→
1000)
3P3W: 4000W (440V
×
5A
×√
3=3810W
→
4000)
3P4W: 4000W (277V
×
5A
×
3=4155W
→
4000)
1
65Hz
*4: If the diameter of the wire is small, the conductor resistance of the wire will be high and the consumption VA of the wire will increase.
Decide wire diameter and wire length so that it does not exceed the rated burden of CT to be connected.