Q&A about specifications
Q
What does “Allowable tolerance” mean?
A
In terms of the amount of electricity, it means a range of tolerances in reading values. For example, when the reading value is “10 kWh,”
a tolerance is ±0.05 kWh. In terms of measured elements other than the amount of electricity, it means a tolerance to the full scale (refer
to page 65). For a current, when a rated current is set to 5 A, ±0.5% of 5 A is a tolerance.
Q
Is accuracy of a CT and a VT included?
A
Accuracy of a CT and a VT is not included in accuracy of the
unit.
A maximum value of tolerance is obtained by summing tolerance of the unit and that of a CT and a VT.
Q
To what degree an area of micro current is measured?
A
A current value is measured from the area exceeding 0.4% of the rated current. In an area below 0.4%, measurement result is indicated
as “0” (zero). However, in that case, still, the amount of electricity is being measured. Even if the indicated value is “0,” measurement
value will increase in continuing measurement for a long time.
The amount of electricity is measured with a load that is about 0.1% or more of all load power.
Q
Is measurement of inverter circuit possible?
A
Measuring the secondary side of the inverter is impossible due to the large fluctuation of frequency
.
Make measurement on the primary side of the inverter. However, since a current waveform on the primary side of the inverter has a
distortion containing the harmonic components, a slight error occurs.
・
Q&A about connection
Q
Does polarity exist in connection between a CT and the unit?
A
Yes.
Make connections so that the polarity of the secondary terminals of a CT and terminal symbols of this unit agree with each other. If
polarity is incorrect, the current value is measurable, but the electric power and the electrical energy cannot be measured correctly.
Q
Are there any key points in avoiding errors in wiring?
A
Check polarity of a CT. And also, check the wiring between the secondary side of a CT and this unit are connected correctly for the 1-side
circuit, 2-side circuit, and 3-side circuit.
Besides, check that voltage inputs for voltage transform unit are connected correctly among P1, P2, P3, and P0.
・
Q&A about setting
Q
Is the setting required?
A
At least, settings of phase wires, primary current and primary voltage are required. Specify settings in accordance with a circuit to be
connected.