Restrictions of measured data
F/W version is displayed in five seconds after the power loading to this device.
Measurement and communication do not performed in a few seconds after the configuration or the change of the rating to it.
Behaviors during operation are as follows:
Measured item
Behaviors of this device
Display part indication
Communication data
Current
Indicate “0A” if RMS value is under 0.4% range of rating.
Indicate upper indication limit value if RMS value is over it.
Same as on the left
Current demand
Indicate upper indication limit value if RMS value is over it.
Same as on the left
Voltage (*1)
Indicate “0V” if RMS value is under 11V.
Indicate upper indication limit value if RMS value is over it.
Same as on the left
Power
Power demand
Reactive power
Apparent power
Indicate “0W”, “0var” or “0VA” if indicated voltage values of all phases
are 0V or indicated current values of them are 0A.
Indicate upper indication limit value if the measured value is over it.
Same as on the left
Power factor
Indicate “100.0%” if indicated voltage values of all phases are 0V or
indicated current values of them are 0A
Same as on the left
Frequency
Voltage condition:
Indicate “----” if voltage V12 (voltage V1N for 3P4W) is 0V.
0
Frequency condition:
Indicate “----” if frequency is under 44.5Hz.
44.5
RMS value of
harmonic current
Voltage condition:
Indicate “----” at all phase if voltage V12 (voltage V1N for 3P4W) is
under 11V.
Indicate “0A” at all phase if voltage V12 (voltage V1N for 3P4W) is
under 40V.
0
0
Frequency condition:
Indicate “----” at all phases if frequency is under 44.5Hz.
0
Content rate of
harmonic current
(modulation
distortion)
Voltage condition:
Indicate “----” at all phase if voltage V12 (voltage V1N for 3P4W) is
under 11V.
Indicate “0.0%” at all phase if voltage V12 (voltage V1N for 3P4W) is
under 40V.
0
0
Frequency condition:
Indicate “----” at all phases if frequency is under 44.5Hz.
Outside-channel error
RMS value of
harmonic voltage
Voltage condition:
Indicate “----” at all phase if voltage V12 (voltage V1N for 3P4W) is
under 11V.
Indicate “0V” at all phase if voltage V12 (voltage V1N for 3P4W) is
under 40V.
0
Frequency condition:
Indicate “----” at all phases if frequency is under 44.5Hz.
0
Content rate of
harmonic voltage
(modulation
distortion)
Voltage condition:
Indicate “----” at all phase if voltage V12 (voltage V1N for 3P4W) is
under 11V.
Indicate “0.0%” at all phase if voltage V12 (voltage V1N for 3P4W) is
under 40V.
0
Frequency condition:
Indicate “----” at all phases if frequency is under 44.5Hz.
0
Pulse count
When use of upper / lower limit alarm = oFF or upper / lower limit alarm
element ≠ pulse count (upper
limit), counting restarts from 0 when
999999 have been exceeded.
When use of upper / lower limit alarm = on and upper / lower limit alarm
element = pulse count (upper limit), it is fixed to 999999 when 999999
have been exceeded.
Same as on the left
Operating time (*2) Indicate “999999h” if operating time is over 999999h.
Same as on the left
Periodic electric
energy
For contact input ON/OFF, integrated value may deviate up to 250 ms
less in time at the start or stop of integration.
Same as on the left
*1: In single-phase, three-wire system, indicate “0V” if RMS value is under 22V.
*2: Operation time is reference value.