Setting menu 4: Upper / lower limit alarm setting, alarm delay time, alarm reset, etc.
In this menu, set the upper / lower alarm, alarm delay time, reset method of alarm clear, etc.
In operating mode, press both and at the same time for more than two seconds to transition to setting
mode and enable the following operations.
Setting menu
Choose the setting menu No. 4.
(As shown in the left figure)
(1) Use of upper /
lower limit alarm
Set the use or non-use of upper / lower limit alarm.
・
If you do not use alarm, choose “oFF” and press to enter setting menu.
・
If you use alarm, choose “on” and press to transition to the setting below.
oFF
(Do not use alarm)
on
(Use alarm)
SET
SET
(2) Upper / lower limit
alarm element
Set the measured element applying upper / lower limit alarm to.
Upper / lower limit alarm of measured value is available by setting this item.
Caution:
1. DA: Current demand, DA(N): N-phase current demand, DW: Electric power demand
V (L-L) : Line voltage, V (L-N) : Phase voltage
2. “DA (N)” and “V (L-N)” are selectable in three-phase 4-wire system
3. “PULSE” is only selectable when you choose “Pulse (PLS.)” on (1) Contact / pulse input of
setting menu No.3.
DA upper limit
DA lower limit
DA (N) upper limit
V (L-L) upper limit
V (L-L) lower limit
V (L-N) upper limit
V (L-N) lower limit
DW upper limit
DW lower limit
PF upper limit
PF lower limit
PULSE upper limit
(3) Upper / lower limit
alarm value
Set the alarm value of upper / lower limit alarm element.
Setting range is as follows:
Measured element
Setting range
Unit
DA upper limit, DA (N) upper limit
0 - 100 (%) of primary current
A
DA lower limit
0 - 100 (%) of primary current
A
V (L-L) upper limit, V (L-N) upper limit
0 - 100 (%) of primary voltage
V
V (L-L) lower limit, V (L-N) lower limit
0 - 100 (%) of primary voltage
V
DW upper limit
-100 - 0 - 100 (%) of full load power
W
DW lower limit
-100 - 0 - 100 (%) of full load power
W
PF upper limit
-50 - 100 - 50 (%)
%
PF lower limit
-50 - 100 - 50 (%)
%
PULSE upper limit
1 – 999999 (Default value is 100000)
For operation of alarm value setting, refer to next section.
SET
DISP
- / RESET
SET
SET
DISP
SET
DISP
SET
DISP