40
Switch
Function
Selection
Default setting*
Function details
Effective timing
Mark
No.
ON (with)
OFF (without)
SW1
1
Manual defrost
ON to start
usual setting
OFF
Switch ON to force defrosting
Always
2
To clear error history
ON to clear
usual setting
OFF
Switch ON to clear (erase) the
following status:
(1)Check codes and Suspension flags in RAM
(2)Check codes and Suspension flags in EEPROM
Always
3
No function
–
–
OFF
–
Always
4
Abnormal disregard
Disregard
Normal
OFF
Check code (P8,UH):
Abnormal detection disregard
5
No function
–
–
OFF
–
–
6
No function
–
–
OFF
–
–
SW4
1
No function
–
–
OFF
–
2
No function
–
–
OFF
–
SW5
1
Silent setting (FAN)
Silent setting (FAN)
usual setting
OFF
Fan speed setting in silent mode
Always
2
Silent setting (Hz)
Silent setting (Hz)
usual setting
OFF
Hz setting in silent mode
3
No function
–
–
OFF
–
–
4
No function
–
–
OFF
–
–
5
Defrost control
selection
For high humidity
Standard
OFF
Switches to optimal defrosting opera
-
tion for low-temperature and high-
humidity regions.
–
6
No function
–
–
OFF
–
–
SW6
1-3
Model Setting
Model
SW6
1
2
3
W50VHA2
1
0
1
1=ON, 0=OFF
As shown in the left
table
–
–
4
Single phase/
3 phase
3 phase
Single phase
OFF
–
–
5-8
Model Setting 2
Model
SW6
5
6
7
8
W50VHA2
1
1
0
0
1=ON, 0=OFF
As shown in the left
table
Make sure to set
SW6-5 to 8 correctly
–
SW7
1
No function
–
–
OFF
–
Always
2
No function
–
–
OFF
–
3-6
No function
–
–
OFF
–
–
SW8
1
Mode selection
Energy saving mode
Powerful mode
OFF
–
Always
2
Max. current setting
Model
Max. current
OFF
ON
W50VHA2
13 A
11 A
OFF
–
When power
supply ON
3
Separate Interface/Flow
temp.controller - outdoor
unit power supplies
Separate power
supply
Outdoor unit power
supply
OFF
Power supply connection method
selection
When power
supply ON
SW9
1-4
No function
–
–
OFF
–
–
<Important Note>
Spare PCBs, however, will be supplied without any settings, which means that all Dip switches are switched OFF.
When servicing, please make sure to set all switches correctly, referring to the previous PCB which is removed from the unit.
*1. Manual defrost should be done as follows.
1
Change the DIP SW1-1 on the outdoor controller board from OFF to ON.
2
Manual defrost will start by the above operation
1
if these conditions written below are satisfied.
• Heat mode setting
• 10 minutes have passed since compressor starts operating or previous manual defrost is finished.
• Pipe temperature is less than or equal to 8
:
.
Manual defrost will finish if certain conditions are satisfied.
Manual defrost can be done if above conditions are satisfied when DIP SW1-1 is changed from OFF to ON.
After DIP SW1-1 is changed from OFF to ON, there is no problem if DIP SW1-1 is left ON or changed to OFF again.
This depends on the service conditions.
8-8. FUNCTION OF SWITCHES
PUHZ-W50VHA2 PUHZ-W50VHA2R1
PUHZ-W50VHA2-BS PUHZ-W50VHA2R1-BS
OCH605A