23
1
2
3
4
5
M
Gray
Orange
Red
Yellow
Black
Parts name
Check points
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature of 10 to 30
:
)
Thermistor (TH3) <Liquid>
Thermistor (TH4) <Discharge>
Thermistor (TH6) <Plate HEX Liquid>
Thermistor (TH7) <Ambient>
Thermistor (TH8) <Heat Sink>
Thermistor (TH32) <Inlet Water>
Thermistor (TH34) <Comp. Surface>
Normal
160 to 410 k
"
4.3 to 9.6 k
"
4.4 to 9.8 k
"
39 to 105 k
"
TH4
TH34
TH3
TH6
TH7
TH32
TH8
Abnormal
Open or short
Measure the resistance between the terminals with a tester.
(At the ambient temperature of 20
:
)
Solenoid valve coil
<4-way valve>
(21S4)
Compressor
(MC)
Normal
Abnormal
Open or short
Refer to “8-4-1. Check method of DC fan motor (fan motor/outdoor controller circuit board)”.
Fan motor (MF1)
2350±170
"
Measure the resistance between the terminals with a tester.
(Winding temperature 20
:
)
Normal
W
V
U
Linear expansion valve
(LEV-A) (LEV-B)
Disconnect the connector then measure the resistance with a tester.
(Winding temperature 20°C)
Normal
Gray - Black
Gray - Red
Gray - Yellow Gray - Orange
Abnormal
46 ± 3
Ω
Open or short
0.640
"
Abnormal
Open or short
8-4. HOW TO CHECK THE PARTS
PUHZ-W50VHA2
PUHZ-W50VHA2R1
PUHZ-W50VHA2-BS PUHZ-W50VHA2R1-BS
OCH605A