29
TH3
Thermistor <Liquid>
V
SP
(Voltage between pins
of C5A, C5B):
0 V DC (when stopped),
DC 1
–
6.5 V
(when operated)
TH32
Thermistor
<Inlet Water>
TH34
<Comp. Surface>
8-6. TEST POINT DIAGRAM
Outdoor controller circuit board
PUHZ-W50VHA2 PUHZ-W50VHA2R1
PUHZ-W50VHA2-BS PUHZ-W50VHA2R1-BS
Communication power
supply D71 Voltage
24 V DC
CNS
S1–S2: 230 V AC
CNAC
2
–
4
:
Power supply for outdoor
controller circuit board
(230 V AC)
1
–
3
:
Power supply for indoor
and outdoor unit connec-
tion wire
(230 V AC)
CNF1, CNF2
Connect to the fan motor
1
–
4
: 280–380 V DC
5
–
4
: 15 V DC
6
–
4
: 0–6.5 V DC
7
–
4
: 15 V DC (When stopped)
7.5 V DC (When operated)
(0–15 V pulse)
21S4
4-way valve
63H
High pressure
switch
SV1
Connection for option
(Drain hose heater output)
CN4
Transmission to out-
door power circuit
board (CN4)
SW6
Model select
SW5
Function switch
SW1
Manual defrost,
detect history
record reset
CNDM
1
–
2
:
Input of low-level
sound priority mode
TH4
Thermistor
<Discharge>
TH7/6
Thermistor
<Ambient/
Plate HEX Liquid>
CNDC
280–380 V DC (
1
+,
3
−)
+ −
V
FG
(Voltage between
right pins of PC5C
and PC5D, pin 3
and pin 4)
(Same as
(CNF1
7
(+)-
4
(−))
SW2
Operation
monitor function
LEV-A,B
Linear expan-
sion valve
SW8
Function switch
CN2
Connect to the outdoor
power circuit board (CN2)
1
–
5
: Reception from
power circuit board
2
–
5
: Zero cross signal
(0–5 V DC)
3
–
4
: 15 V DC
6
–
5
: 16 V DC
7
–
5
: 16 V DC
<CAUTION> TEST POINT
1
is high voltage.
OCH605A