DISASSEMBLY PROCEDURE
PHOTOS/FIGURES
28.
How to remove the mixing valve (ERST17D-***BD
model)
(1) Remove the front panel. (Refer to Procedure 1.)
(2) Disconnect
the relay connector
(Mixing valve) under the
control box. (Photo 4-4)
(3) Release the water pump lead wire from the cable clamp,
the fastener and the cable strap in the control box, and the
cable strap, the fastener and the band below the control
box. (Photos 4-1, 10-6 and 28-1)
(4) Pull the mixing valve motor and remove it.
(5) Remove the mixing valve body by removing the three G1"
nuts using the 2 spanners: one to hold the G1" nut and
the other to turn the other side of G1" nut.
Remove the mixing valve by sliding it vertical. (Photo 28-2)
• When reinstalling the G1" nuts, use new G1" gaskets.
• Be sure to change the pump and the mixing valve lead
wire together.
• Be sure to wipe water around the surface of the pump
and the water pump lead wire thoroughly.
Note:
Before replacing the mixing valve, be sure to power off the
cylinder unit.
Failure to do so may cause electric shock or cause the mixing
valve to malfunction.
Photo 28-1
Photo 28-2
29.
How to remove the magnetic filter (ERST17D-***BD
model)
(1) Remove the front panel. (Refer to Procedure 1.)
(2) Detach the 2 quick connections. (Photos 29)
• When reinstalling the quick connections, use new
O-rings.
• Refer to Procedure 25 for how to attach and detach the
quick connection.
(3) Remove the Magnetic filter by carefully pulling it. (Photo
29)
Photo 29
93
OCH714D
O-ring
Mixing valve motor
Cable strap
Mixing valve body
Quick connection
Quick connection
Magnetic filer