10
OCH714D
<T
able 3.4>
*1 V
olume of sanitary water circuit, primary DHW circuit (from 3-way valve to confluent point with heating circuit), piping to expansion vessel, and expansion vessel are not included in this value.
*2
The environment must be frost-free.
*3
See outdoor unit spec table (min, 10
°C
). Cooling mode is not available in low outdoor temperature. If you use our system in cooling mode at the low ambient temperature (10°C or below), there are some risks of plate heat exchanger damages by frozen water
.
*4 For the model without booster heater and immersion heater
, the maximum allowable hot water temperature is [Maximum outlet water of outdoor unit -3
°C]. For the maximum outlet water of outdoor unit, refer to outdoor unit data book.
*5
Do not fit immersion heaters without thermal cut-out. Use only Mitsubishi Electric service parts as a direct replacement.
Model name
EHPT17X-
VM2D
EHPT17X-
VM6D
EHPT17X-
YM9D
ERPT17X-
VM2D
EHPT20X-
MED
EHPT20X-
VM6D
EHPT20X-
YM9D
EHPT20X- YM9ED
EHPT20X-
TM9D
EHPT20X- MHEDW
ERPT20X-
MD
ERPT20X-
VM2D
ERPT20X-
VM6D
EHPT30X-
MED
EHPT30X- YM9ED
ERPT30X- VM2ED
ERPT30X- VM6ED
Nominal domestic hot water volume
170 L
200 L
300 L
Overall unit dimensions (Height × Width × Depth)
1400 × 595 × 680 mm
1600 × 595 × 680 mm
2050 × 595 × 680 mm
W
eight (empty)
86 kg
87 kg
89 kg
86 kg
87 kg
94 kg
96 kg
90 kg
96 kg
94 kg
93 kg
94 kg
95 kg
106 kg
110 kg
107 kg
108 kg
W
eight (full)
262 kg
263 kg
267 kg
262 kg
293 kg
301 kg
304 kg
299 kg
304 kg
300 kg
299 kg
300 kg
301 kg
413 kg
419 kg
414 kg
415 kg
W
ater volume of heating circuit in the unit *1
3.2 L
5.5 L
3.2 L
3.7 L
6.0 L
3.7 L
3.7 L
4.4 L
6.7 L
4.4 L
Unvented expansion
vessel(Primary heating)
Nominal volume
12 L
—
12 L
—
12 L
—
12 L
—
Charge pressure
0.1 MPa
—
0.1 MPa
—
0.1 MPa
—
0.1 MPa
—
Safety device
Primary circuit
Control thermistor
80°C
Pressure relief valve
—
Flow sensor
Min. flow 5.0 L/min
BH manual reset thermostat
90°C
—
90°C
90°C
—
—
90°C
—
90°C
BH thermal Cut Of
f
121°C
—
121°C
121°C
—
—
121°C
—
121°C
DHW tank
Control thermistor
75
°C
IH manual reset thermostat
—
Temperature/
Pressure relief valve
1.0 MPa (10 bar)
90°C /
0.7 MPa (7 bar)
1.0 MPa (10 bar)
Connections
W
ater
Primary circuit
ø28 mm
DHW circuit
ø22 mm
Refrigerant
(R32/ R410A)
Liquid
—
Gas
—
Operating range
Heating
Room temperature
10 - 30°C
Flow temperature
20 - 60°C
Cooling
Room temperature
—
Flow temperature
—
5 - 25°C
—
5 - 25°C
—
5 - 25°C
Guaranteed operat
-
ing range *2
Ambient
0 - 35°C (
80 %RH)
Outdoor temperature
Heating
See outdoor unit spec table.
Cooling
—
*3
—
*3
—
*3
DHW tank performance
Maximum allowable hot water temperature
70°C
*4
70°C
*4
70°C
*4
70°C
Declared load profile
L
L
XL
Average climate
W
ater heater energy efficiency
class
A+
A+
A
Electrical data
Control board (Including 4 pumps)
Power supply
(Phase, voltage, frequency)
~/N, 230 V
, 50 Hz
Input
0.30 kW
0.34 kW
Current
1.95 A
2.56 A
Breaker
10 A
Booster heater
Power supply
(Phase, voltage, frequency)
~/N, 230 V
,
50 Hz
3~, 400 V
,
50 Hz
~/N, 230 V
,
50 Hz
—
~/N, 230 V
,
50 Hz
3~, 400 V
,
50 Hz
3~, 230 V
,
50 Hz
—
—
~/N, 230 V
,
50 Hz
—
3~, 400 V
,
50 Hz
~/N, 230 V
,
50 Hz
Capacity
2 kW
2 kW +4 kW
3 kW +6 kW
2 kW
—
2 kW +4 kW
3 kW +6 kW
—
—
2 kW
2 kW +4 kW
—
3 kW +6 kW
2 kW
2 kW +4 kW
Heater step
1
3
1
—
3
3
—
—
1
3
—
3
1
3
Current
9 A
26 A
13 A
9 A
—
26 A
13 A
23 A
—
—
9 A
26 A
—
13 A
9 A
26 A
Breaker
16 A
32 A
16 A
16 A
—
32 A
16 A
32 A
—
—
16 A
32 A
—
16 A
16 A
32 A
Immersion heater *5
Power supply
(Phase, voltage, frequency)
—
~/N, 230 V, 50 Hz
—
Capacity
—
3 kW
—
Current
—
13 A
—
Breaker
—
16 A
—
Sound power level (PWL)
40 dB(A)