background image

D700 QUICK START MANUAL 

5

FR-D710W-042 
FR-D720-070 or more
FR-D740-012 or more
FR-D720S-070, 100

NOTE
•  When encasing multiple inverters, install them in parallel as a 

cooling measure.

•  When using the inverters at the surrounding air temperature of 40°C 

(104°F) or less, the inverters can be installed without any clearance 
between them (0cm (0 inches) clearance). When surrounding 
air temperature exceeds 40°C (104°F), clearances between the 
inverters should be 1cm (0.39 inches) or more (5cm (1.96 inches) or 
more for the FR-D720-238 and FR-D740-120, or more).

•  Install the inverter vertically.

2.1  PRODUCT CHECKING AND PARTS IDENTIFICATION

n

 GENERAL PRECAUTION

The bus capacitor discharge time is 10 minutes. Before starting wiring 
or inspection, switch power off, wait for more than 10 minutes, and 
check for residual voltage between terminal P/+ and N/- with a meter 
etc., to avoid a hazard of electrical shock.

n

 ENVIRONMENT

Before installation, check that the environment meets following 
specifications.

Surrounding Air 

Temperature

-10°C to +50°C  

(14°F to 122°F)  

(non-freezing)

Ambient Humidity 90% RH maximum
Storage 

Temperature

-20°C to +65°C (-4°F to 149°F) (Temperature applicable for a 

short time, e.g. in transit.)

Ambience

Indoors (free from corrosive gas, flammable gas, oil mist, dust 

and dirt)

Altitude, Vibration

Maximum 1000m (3280.80 feet) above sea level for standard 

operation. After that derate by 3% for every extra 500m (1640.40 

feet) up to 2500m (8202 feet) (91%).

5.9m/s² or less

NOTE
•  Install the inverter on a strong surface securely and vertically with 

bolts.

•  Leave enough clearances and take cooling measures.
•  Avoid places where the inverter is subjected to direct sunlight, high 

temperature and high humidity.

•  Install the inverter on a non-combustible wall surface.

3. OUTLINE DIMENSION DRAWINGS

Single-phase 110V class

Inverter Type

W

W1

H

H1

D

FR-D710W-008

68 (2.68)

56 (2.20)

128 (5.04)

118 (4.65)

80.5 (3.17)

FR-D710W-014

110.5 (4.35)

FR-D710W-025

142.5( 5.61)

FR-D710W-042 108 (4.25)

96 (3.78)

149.5 (5.89)

Three-phase 200V class

Inverter Type

W

W1

H

H1

D

FR-D720-008

68 (2.68)

56 (2.20)

128 (5.04)

118 (4.65)

80.5 (3.17)

FR-D720-014
FR-D720-025

112.5 (4.43)

FR-D720-042

132.5 (5.22)

FR-D720-070

108 (4.25)

96 (3.78)

135.5 (5.34)

FR-D720-100
FR-D720-165

170 (6.69)

158 (6.22)

142.5( 5.61)

FR-D720-238

220 (8.66)

208 (8.19)

150 (5.91)

138 (5.43)

155 (6.10)

FR-D720-318

Three-phase 400V class

Inverter Type

W

W1

H

H1

D

FR-D740-012

108 (4.25)

96 (3.78)

128 (5.04)

118 (4.65)

129.5 (5.10)

FR-D740-022
FR-D740-036

135.5 (5.34)

FR-D740-050

155.5 (6.12)

FR-D740-080

165.5 (6.52)

FR-D740-120

220 (8.66)

208 (8.19)

150 (5.91)

138 (5.43)

155 (6.10)

FR-D740-160

Three-phase 200V class

Inverter Type

W

W1

H

H1

D

FR-D720S-008

68 (2.68)

56 (2.20)

128 (5.04)

118 (4.65)

80.5 (3.17)

FR-D720S-014
FR-D720S-025

142.5 (5.61)

FR-D720S-042

162.5 (6.40)

FR-D720S-070 108 (4.25)

96 (3.78)

155.5 (6.12)

FR-D720S-100 140 (5.51)

128 (5.04)

150 (5.91)

138 (5.43)

145 (5.71)

Front cover

Wiring cover

10cm(3.94inches)

 or more

10cm(3.94inches)

 or more

Vertical

Refer to the clearances

on the left.

5cm

(1.97 inches)

5cm

(1.97 inches)

5cm

(1.97 inches)

Measurement 

position

Measurement 

position

Inverter

(Unit:mm (inches))

W1

W

H1

H

D

MitsubishiElectric Automation, Inc.

Содержание D700

Страница 1: ...VARIABLE FREQUENCY DRIVE MODEL D700 QUICK START MANUAL MitsubishiElectric Automation Inc ...

Страница 2: ...TING PLATE 4 2 INSTALLATION OF THE INVERTER 4 2 1 PRODUCT CHECKING AND PARTS IDENTIFICATION 5 3 OUTLINE DIMENSION DRAWINGS 5 4 WIRING 6 5 PRECAUTIONS FOR USE OF THE INVERTER 6 6 FAILSAFE OF THE SYSTEM WHICH USES THE INVERTER 7 7 PARAMETER LIST 7 8 OPERATION PANEL 10 MitsubishiElectric Automation Inc ...

Страница 3: ... Do not change the cooling fan while power is on It is dangerous to change the cooling fan while power is on Do not touch the printed circuit board with wet hands Otherwise you may get an electric shock When measuring the main circuit capacitor capacity the DC voltage is applied to the motor for 1s at powering off Never touch the motor terminal etc right after powering off to prevent an electric s...

Страница 4: ...rminals deteriorating the insulation of the motor When parameter clear or all parameter clear is performed reset the required parameters before starting operations Each parameter returns to the initial value The inverter can be easily set for high speed operation Before changing its setting fully examine the performances of the motor and machine In addition to the inverter s holding function insta...

Страница 5: ...OTE Install the inverter on a strong surface securely and vertically with bolts Leave enough clearances and take cooling measures Avoid places where the inverter is subjected to direct sunlight high temperature and high humidity Install the inverter on a non combustible wall surface 3 OUTLINE DIMENSION DRAWINGS Single phase 110V class Inverter Type W W1 H H1 D FR D710W 008 68 2 68 56 2 20 128 5 04...

Страница 6: ...nd insulation and phase to phase insulation of the inverter output side before power on Especially for an old motor or use in hostile atmosphere securely check the motor insulation resistance etc 10 Do not use the inverter input side magnetic contactor to start stop the inverter Always use the start signal turn ON OFF STF STR signal to start stop the inverter 11 Across P and PR terminals connect o...

Страница 7: ...nning signal Start signal STF signal STR signal Running signal RUN signal 4 Inverter running status Logic check of the start signal and output current Start signal STF signal STR signal Output current detection signal Y12 signal Backup method outside the inverter Even if the interlock is provided by the inverter status signal enough failsafe is not ensured depending on the failure status of the in...

Страница 8: ...eference 0 to 500A Rated inverter current 57 Restart coasting time 0 0 1 to 5s 9999 9999 58 Restart cushion time 0 to 60s 1s 59 Remote function selection 0 1 2 3 0 Parameter Name Setting Range Initial Value 60 Energy saving control selection 0 9 0 0 9 0 65 Retry selection 0 to 5 0 66 Stall prevention operation reduction starting frequency 0 to 400Hz 60Hz 67 Number of retries at fault occurrence 0 ...

Страница 9: ... speed 11 0 to 400Hz 9999 9999 236 Multi speed setting speed 12 0 to 400Hz 9999 9999 237 Multi speed setting speed 13 0 to 400Hz 9999 9999 238 Multi speed setting speed 14 0 to 400Hz 9999 9999 239 Multi speed setting speed 15 0 to 400Hz 9999 9999 240 Soft PWM operation selection 0 1 0 241 Analog input display unit switchover 0 1 1 244 Cooling fan operation selection 0 1 1 245 Rated slip 0 to 50 99...

Страница 10: ...18 FR D740 012 to 160 FR D720S 025 to 100 4 The parameter number in parentheses is the one for use with the operation panel FR PA02 02 for the FR E500 series or parameter unit FR PU04 FR PU07 5 The initial value differs according to the voltage class 200V class 400V class 6 Available only for the three phase power input specification model 8 OPERATION PANEL The operation panel cannot be removed fr...

Страница 11: ...operate with Setting Dial y a l p s i D n o i t a r e p O 1 Screen at powering on The monitor display appears 2 Press and for 0 5s 3 Turn until appears refer to the table below for other settings 4 Press to set Flicker Parameter setting complete The monitor display appears after 3s Flickering Flickering Flickering Operation Panel Indication Operation Method Start command Frequency command External...

Страница 12: ...layed nor set n SETTING DIAL PUSH Push the setting dial to display the set frequency currently set Appears when PU operation mode or external PU combined operation mode 1 is selected Pr 79 3 y a l p s i D n o i t a r e p O 1 Screen at powering on The monitor display appears 2 Press to choose the PU operation mode PU indication is lit 3 Press to choose the parameter setting mode PRM indication is l...

Страница 13: ...ernon Hills IL 60061 Ph 847 478 2100 Fx 847 478 2253 us MitsubishiElectric com fa en support January 2016 2016 Mitsubishi Electric Automation Inc Specifications subject to change without notice All rights reserved AZ IB 0600367ENG A MitsubishiElectric Automation Inc ...

Отзывы: