Parameter 

Name 

Setting

Range

Initial Value

146

Parameter for manufacturer setting. Do not set.

150

Output current detection level

0 to 200%

150%

151

Output current detection signal 

delay time

0 to 10s

0s

152

Zero current detection level

0 to 200% 

5%

153

Zero current detection time

0 to 1s

0.5s

156

Stall prevention operation selection

0 to 31, 100, 

101

0

157

OL signal output timer

0 to 25s, 9999

0s

158

AM terminal function selection

1 to 3, 5, 8 to 

12, 14, 21, 24, 

52, 53, 61, 62

1

*160

Extended function display selection 0, 9999

0

161

Frequency setting/key lock 

operation selection

0, 1, 10, 11

0

162

Automatic restart after 

instantaneous power failure 

selection

0, 1, 10, 11

1

165

Stall prevention operation level for 

restart

0 to 200%

150%

166

Output current detection signal 

retention time

0 to 10s, 9999

0.1s

167

Output current detection operation 

selection

0, 1

0

168

Parameter for manufacturer setting. Do not set.

169
170

Watt-hour meter clear

0, 10, 9999

9999

171

Operation hour meter clear

0, 9999

9999

178

STF terminal function selection

0 to 5, 7, 8, 10, 

12, 14, 16, 18, 

24, 25, 60, 62, 

65 to 67, 9999

60

179

STR terminal function selection

0 to 5, 7, 8, 10, 

12, 14, 16, 18, 

24, 25, 61, 62, 

65 to 67, 9999

61

180

RL terminal function selection

0 to 5, 7, 8, 10, 

12, 14, 16, 18, 

24, 25, 62, 65 

to 67, 9999

0

181

RM terminal function selection

1

182

RH terminal function selection

2

190

RUN terminal function selection

0, 1, 3, 4, 7, 8, 

11 to 16, 25, 

26, 46, 47, 64, 

70, 80, 90, 91, 

93, 95, 96, 98, 

99,  101, 103, 

104, 107, 108, 

111 to 116, 125, 

126, 146, 147, 

164, 170, 180, 

190, 191, 193, 

195, 196, 198, 

199, 9999

0

192

A,B,C terminal function selection

0, 1, 3, 4, 7, 8, 

11 to 16, 25, 

26, 46, 47, 64, 

70, 80, 90, 91, 

95, 96, 98, 99, 

100, 101, 103, 

104, 107, 108, 

111 to 116, 125, 

126, 146, 147, 

164, 170, 180, 

190, 191, 195, 

196, 198, 199, 

9999

99

232

Multi-speed setting (speed 8)

0 to 400Hz, 

9999

9999

233

Multi-speed setting (speed 9)

0 to 400Hz, 

9999

9999

234

Multi-speed setting (speed 10)

0 to 400Hz, 

9999

9999

Parameter 

Name 

Setting

Range

Initial Value

235

Multi-speed setting (speed 11)

0 to 400Hz, 

9999

9999

236

Multi-speed setting (speed 12)

0 to 400Hz, 

9999

9999

237

Multi-speed setting (speed 13)

0 to 400Hz, 

9999

9999

238

Multi-speed setting (speed 14)

0 to 400Hz, 

9999

9999

239

Multi-speed setting (speed 15)

0 to 400Hz, 

9999

9999

240

Soft-PWM operation selection

0, 1

0

241

Analog input display unit switchover 0, 1

1

244

Cooling fan operation selection

0, 1

1

245

Rated slip

0 to 50%, 9999 9999

246

Slip compensation time constant

0.01 to 10s

0.5s

247

Constant-power range slip 

compensation selection

0, 9999

9999

249

Earth (ground) fault detection at 

start

0, 1

0

250

Stop selection

0 to 100s, 1000 

to 1100s, 8888, 

9999

9999

251

Output phase loss protection 

selection

0, 1

1

255

Life alarm status display

(0 to 15) 

0

256

Inrush current limit circuit life display (0 to 100%) 

100%

257

Control circuit capacitor life display

(0 to 100%) 

100%

258

Main circuit capacitor life display

(0 to 100%) 

100%

259

Main circuit capacitor life measuring 0, 1 (2, 3, 8, 9)  0

260

PWM frequency automatic 

switchover

0, 1

0

261

Power failure stop selection

0, 1, 2

0

267

Terminal 4 input selection

0, 1, 2

0

268

Monitor decimal digits selection

0, 1, 9999

9999

269

Parameter for manufacturer setting. Do not set.

295

Magnitude of frequency change 

setting

0, 0.01, 0.10, 

1.00, 10.00

0

296

Password lock level

1 to 6, 101 to 

106, 9999

9999

297

Password lock/unlock

1000 to 9998 (0 

to 5, 9999)

9999

298

Frequency search gain

0 to 32767, 

9999

9999

299

Rotation direction detection 

selection at restarting

0, 1, 9999

0

338

Communication operation 

command source

0, 1

0

339

Communication frequency 

command source

0, 1, 2

0

340

Communication startup mode 

selection

0, 1, 10

0

342

Communication EEPROM write 

selection

0, 1

0

343

Communication error count

-

0

450

Second applied motor

0, 1, 9999

9999

495

Remote output selection

0, 1, 10, 11

0

496

Remote output data 1

0 to 4095

0

502

Stop mode selection at 

communication error

0, 1, 2

0

503

Maintenance timer

0 (1 to 9998)

0

504

Maintenance timer alarm output 

set time

0 to 9998, 9999 9999

549

Protocol selection

0, 1

0

551

PU mode operation command 

source selection

2, 4, 9999

9999

555

555 Current average time

0.1 to 1s

1s

556

Data output mask time

0 to 20s

1s

MitsubishiElectric Automation, Inc.

Содержание D700

Страница 1: ...VARIABLE FREQUENCY DRIVE MODEL D700 QUICK START MANUAL MitsubishiElectric Automation Inc ...

Страница 2: ...TING PLATE 4 2 INSTALLATION OF THE INVERTER 4 2 1 PRODUCT CHECKING AND PARTS IDENTIFICATION 5 3 OUTLINE DIMENSION DRAWINGS 5 4 WIRING 6 5 PRECAUTIONS FOR USE OF THE INVERTER 6 6 FAILSAFE OF THE SYSTEM WHICH USES THE INVERTER 7 7 PARAMETER LIST 7 8 OPERATION PANEL 10 MitsubishiElectric Automation Inc ...

Страница 3: ... Do not change the cooling fan while power is on It is dangerous to change the cooling fan while power is on Do not touch the printed circuit board with wet hands Otherwise you may get an electric shock When measuring the main circuit capacitor capacity the DC voltage is applied to the motor for 1s at powering off Never touch the motor terminal etc right after powering off to prevent an electric s...

Страница 4: ...rminals deteriorating the insulation of the motor When parameter clear or all parameter clear is performed reset the required parameters before starting operations Each parameter returns to the initial value The inverter can be easily set for high speed operation Before changing its setting fully examine the performances of the motor and machine In addition to the inverter s holding function insta...

Страница 5: ...OTE Install the inverter on a strong surface securely and vertically with bolts Leave enough clearances and take cooling measures Avoid places where the inverter is subjected to direct sunlight high temperature and high humidity Install the inverter on a non combustible wall surface 3 OUTLINE DIMENSION DRAWINGS Single phase 110V class Inverter Type W W1 H H1 D FR D710W 008 68 2 68 56 2 20 128 5 04...

Страница 6: ...nd insulation and phase to phase insulation of the inverter output side before power on Especially for an old motor or use in hostile atmosphere securely check the motor insulation resistance etc 10 Do not use the inverter input side magnetic contactor to start stop the inverter Always use the start signal turn ON OFF STF STR signal to start stop the inverter 11 Across P and PR terminals connect o...

Страница 7: ...nning signal Start signal STF signal STR signal Running signal RUN signal 4 Inverter running status Logic check of the start signal and output current Start signal STF signal STR signal Output current detection signal Y12 signal Backup method outside the inverter Even if the interlock is provided by the inverter status signal enough failsafe is not ensured depending on the failure status of the in...

Страница 8: ...eference 0 to 500A Rated inverter current 57 Restart coasting time 0 0 1 to 5s 9999 9999 58 Restart cushion time 0 to 60s 1s 59 Remote function selection 0 1 2 3 0 Parameter Name Setting Range Initial Value 60 Energy saving control selection 0 9 0 0 9 0 65 Retry selection 0 to 5 0 66 Stall prevention operation reduction starting frequency 0 to 400Hz 60Hz 67 Number of retries at fault occurrence 0 ...

Страница 9: ... speed 11 0 to 400Hz 9999 9999 236 Multi speed setting speed 12 0 to 400Hz 9999 9999 237 Multi speed setting speed 13 0 to 400Hz 9999 9999 238 Multi speed setting speed 14 0 to 400Hz 9999 9999 239 Multi speed setting speed 15 0 to 400Hz 9999 9999 240 Soft PWM operation selection 0 1 0 241 Analog input display unit switchover 0 1 1 244 Cooling fan operation selection 0 1 1 245 Rated slip 0 to 50 99...

Страница 10: ...18 FR D740 012 to 160 FR D720S 025 to 100 4 The parameter number in parentheses is the one for use with the operation panel FR PA02 02 for the FR E500 series or parameter unit FR PU04 FR PU07 5 The initial value differs according to the voltage class 200V class 400V class 6 Available only for the three phase power input specification model 8 OPERATION PANEL The operation panel cannot be removed fr...

Страница 11: ...operate with Setting Dial y a l p s i D n o i t a r e p O 1 Screen at powering on The monitor display appears 2 Press and for 0 5s 3 Turn until appears refer to the table below for other settings 4 Press to set Flicker Parameter setting complete The monitor display appears after 3s Flickering Flickering Flickering Operation Panel Indication Operation Method Start command Frequency command External...

Страница 12: ...layed nor set n SETTING DIAL PUSH Push the setting dial to display the set frequency currently set Appears when PU operation mode or external PU combined operation mode 1 is selected Pr 79 3 y a l p s i D n o i t a r e p O 1 Screen at powering on The monitor display appears 2 Press to choose the PU operation mode PU indication is lit 3 Press to choose the parameter setting mode PRM indication is l...

Страница 13: ...ernon Hills IL 60061 Ph 847 478 2100 Fx 847 478 2253 us MitsubishiElectric com fa en support January 2016 2016 Mitsubishi Electric Automation Inc Specifications subject to change without notice All rights reserved AZ IB 0600367ENG A MitsubishiElectric Automation Inc ...

Отзывы: