VIII
Troubleshooting ]
- 87 -
HWE09070
GB
[3] Troubleshooting Principal Parts
-1- LEV
LEV operation
LEV are stepping-motor-driven valves that operate by receiving the pulse signals from the indoor and outdoor unit control
boards.
(1) Indoor LEV and BC controller LEV
The valve opening changes according to the number of pulses.
1) Control boards and the LEV
2) Pulse signal output and valve operation
3) LEV valve closing and opening operation
Indoor unit connector CN60
Control board CNLV1,CNLV2
Connector
4
3
2
1
Intermediate connector
Red
Brown
Blue
Orange
Yellow
White
Outdoor control board
DC12V
6
5
4
3
2
1
Drive circuit
4
3
2
1
LEV
M
5
2
1
3
4
6
Red Orange
White
Brown
Blue
Yellow
Note. The connector numbers on the intermediate connector and the connector on the control board differ. Check the color of the lead wire
to judge the number.
5
2
1
3
4
6
Output state
Output
(phase)
number
1
2
3
4
1
ON OFF OFF ON
2
ON ON OFF OFF
3
OFF ON ON OFF
4
OFF OFF ON ON
Output pulses change in the following orders when the
Valve is closed; 1 2 3 4 1
Valve is open; 4 3 2 1 4
*1. When the LEV opening angle does not change,
all the output phases will be off.
*2. When the output is open phase or remains ON,
the motor cannot run smoothly, and rattles and vibrates.
*When the power is turned on, the valve closing signal of 2200 pulses
will be output from the indoor board to LEV to fix the valve position.
It must be fixed at point A.
When the valve operates smoothly, no sound from LEV or no vibration
occurs, however, when the pulses change from E to A in the chart or
the valve is locked, a big sound occurs.
*Whether a sound is generated or not can be determined by
holding a screwdriver against it, then placing your ear against the handle.
Valve opening (refrigerant flow rate)
Valve closed
Valve open
E
B
80 - 100 pulses
Pulses
Fully open: 1400 pulses
A
C
D
Содержание CMB-PW202V-J
Страница 1: ...Service Handbook AIR CONDITIONERS MODEL CMB PW202V J ...
Страница 9: ...HWE09070 GB ...
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 28: ... II Restrictions 19 HWE09070 GB ...
Страница 31: ... 22 II Restrictions GB HWE09070 ...
Страница 36: ... 27 HWE09070 GB III WCB Components 1 WCB Components 29 2 Control Box of the WCB 30 3 WCB Circuit Board 31 ...
Страница 37: ... 28 ...
Страница 40: ... III WCB Components 31 HWE09070 GB 3 WCB Circuit Board SW1 SW2 SW5 SW6 SW4 ...
Страница 41: ... 32 III WCB Components GB HWE09070 ...
Страница 42: ... 33 HWE09070 GB IV Electrical Wiring Diagram 1 Electrical Wiring Diagram of the WCB 35 ...
Страница 43: ... 34 ...
Страница 45: ... 36 IV Electrical Wiring Diagram GB HWE09070 ...
Страница 46: ... 37 HWE09070 GB V Refrigerant Circuit 1 Refrigerant Circuit Diagram 39 2 Principal Parts and Functions 40 ...
Страница 47: ... 38 ...
Страница 51: ... 42 ...
Страница 61: ... 52 VI Control GB HWE09070 ...
Страница 63: ... 54 ...
Страница 73: ... 64 ...
Страница 108: ... 99 HWE09070 GB IX LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 101 ...
Страница 109: ... 100 ...