II
Restrictions ]
21
- 21 -
HWE09070
GB
(4) Wiring method
1) Indoor/outdoor transmission line
Daisy-chain terminals M1 and M2 of the terminal block
for indoor-outdoor transmission line (TB3) on the outdoor
units (OC), of the terminal block for indoor-outdoor trans-
mission line (TB02) on the WCB (BC), and of the terminal
block for indoor-outdoor transmission line (TB5) on each
indoor unit (IC). (Non-polarized two-wire)
Only use shielded cables.
Shielded cable connection
Daisy-chain the ground terminal ( ) on the outdoo-
runits (OC), the S terminal of the terminal block(TB02) on
the BC controller (BC), and the S terminal of the terminal
block (TB5) on the indoor unit (IC) with the shielded ca-
ble.
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Connect terminals 1 and 2 on the terminal block for MA
remote controller line (TB15) on the indoor unit (IC) to the
terminal block on the MA remote controller (MA).
(Non-polarized two-wire)
When 2 remote controllers are connected to the sys-
tem
When 2 remote controllers are connected to the system,
connect terminals 1 and 2 of the terminal block (TB15) on
the indoor unit (IC) to the terminal block on the two MA
remote controllers.
Set one of the MA remote controllers as a sub controller.
(Refer to the Instruction Manual for the MA remote con-
troller for the setting method.)
Group operation of indoor units
To perform a group operation of indoor units (IC), daisy-
chain terminals 1 and 2 on the terminal block (TB15) on
all indoor units (IC) in the same group, and then connect
terminals 1 and 2 on the terminal block (TB15) on the in-
door unit on one end to the terminal block on the MA re-
motecontroller. (Non-polarized two-wire)
When performing a group operation of indoor units that
have different functions, "Automatic indoor/outdoor ad-
dresssetup" is not available.
4) LOSSNAY connection
Connect terminals M1 and M2 on the terminal
block(TB5) on the indoor unit (IC) to the appropriate ter-
minals on the terminal block (TB5) on LOSSNAY (LC).
(Non-polarized two-wire)
Interlock operation setting with all the indoor units in the
same system will automatically be made. (It is required
that the Lossnay unit be turned on before the outdoo-
runit.)
When performing an interlocked operation of part of the
indoor units in the system with a LOSSNAY unit, using a
LOSSNAY unit alone without interlocking it with any
units, performing an interlock operation of more than 16
indoor units with a LOSSNAY unit, or connecting two or
more LOSSNAY units to the same refrigerant system,
the automatic IC/OC address setup function is not avail-
able.
5) Switch setting
No address settings required.
(5) Address setting method
The port number setting is required to connect to the indoor units as shown below.
Port for Indoor unit/PWFY: Port number "0"
Port for PWFY: Port number "1"
Proce-
dures
Unit or controller
Address set-
ting range
Setting method
Notes
Factory
setting
1
Indoor unit
Main unit
IC
No settings
required.
-
Port number setting is re-
quired (Note)
To perform a group opera-
tion of indoor units that fea-
ture different functions, the
automatic IC/OC address
setup function is not avail-
able.
00
Sub unit
IC
2
LOSSNAY
LC
No settings
required.
-
00
3
MA
remote con-
troller
Main
remote con-
troller
MA
No settings
required.
-
Main
Sub
remote con-
troller
MA
Sub
remote con-
troller
Settings to be
made with the
Sub/Main
switch
4
Outdoor unit
OC
No settings
required.
-
00
5
Auxiliary
outdoor unit
WCB
BC
No settings
required.
-
00
Содержание CMB-PW202V-J
Страница 1: ...Service Handbook AIR CONDITIONERS MODEL CMB PW202V J ...
Страница 9: ...HWE09070 GB ...
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 28: ... II Restrictions 19 HWE09070 GB ...
Страница 31: ... 22 II Restrictions GB HWE09070 ...
Страница 36: ... 27 HWE09070 GB III WCB Components 1 WCB Components 29 2 Control Box of the WCB 30 3 WCB Circuit Board 31 ...
Страница 37: ... 28 ...
Страница 40: ... III WCB Components 31 HWE09070 GB 3 WCB Circuit Board SW1 SW2 SW5 SW6 SW4 ...
Страница 41: ... 32 III WCB Components GB HWE09070 ...
Страница 42: ... 33 HWE09070 GB IV Electrical Wiring Diagram 1 Electrical Wiring Diagram of the WCB 35 ...
Страница 43: ... 34 ...
Страница 45: ... 36 IV Electrical Wiring Diagram GB HWE09070 ...
Страница 46: ... 37 HWE09070 GB V Refrigerant Circuit 1 Refrigerant Circuit Diagram 39 2 Principal Parts and Functions 40 ...
Страница 47: ... 38 ...
Страница 51: ... 42 ...
Страница 61: ... 52 VI Control GB HWE09070 ...
Страница 63: ... 54 ...
Страница 73: ... 64 ...
Страница 108: ... 99 HWE09070 GB IX LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 101 ...
Страница 109: ... 100 ...