VIII
Troubleshooting ]
- 72 -
HWE09070
GB
1. Error
Code
No ACK error
2. Error
definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans-
mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide
the response (ACK).
3. System
configuration
(1) System with one outdoor unit
6607
Error
source
address
Error dis-
play
Detection
method
Cause
Check method and remedy
Outdoor
unit (OC)
ME re-
mote con-
troller
(RC)
MA re-
mote con-
troller
(MA)
No ac-
knowl-
edgement
(ACK) at
IC trans-
mission to
OC
(1)
Contact failure of transmission line of OC or IC
Turn off the power
source of the outdoor
unit, and turn it on again.
If the error is accidental,
it will run normally. If not,
check the causes (1) -
(4).
(2)
Decrease of transmission line voltage/signal by ex-
ceeding acceptable range of transmission wiring.
Farthest:200 m [656ft] or less
Remote controller wiring:10m [32ft] or less
(3)
Erroneous sizing of transmission line (Not within the
range below). Wire diameter:
1.25mm
2
[AWG16] or more
(4)
Indoor unit control board failure
WCB
(BC)
ME re-
mote con-
troller
(RC)
MA re-
mote con-
troller
(MA)
No ac-
knowl-
edgement
(ACK) at
IC trans-
mission to
BC
(1)
When WCB address is changed or modified during
operation.
Keep the power to the
outdoor units and WCB
turned off simultaneous-
ly for at least five min-
utes, and turn them
back on.
If the error is accidental,
they will run normally. If
not, check the causes
(1) - (4).
(2)
Faulty or disconnected transmission wiring of WCB
(3)
Disconnected connector of WCB (CN02)
(4)
Faulty control board of WCB
Indoor
unit (IC)
ME re-
mote con-
troller
(RC)
MA re-
mote con-
troller
(MA)
No ac-
knowl-
edgement
(ACK) at
RC trans-
mission to
IC
(1)
When IC unit address is changed or modified during
operation.
Turn off the outdoor/in-
door units for 5 or more
minutes, and turn them
on again.
If the error is accidental,
they will run normally.
If not, check the causes
(1) - (5).
(2)
Faulty or disconnected IC transmission wiring
(3)
Disconnected IC connector
(CN2M)
(4)
Indoor unit controller failure
(5)
ME remote controller failure
LOSS-
NAY
(LC)
ME re-
mote con-
troller
(RC)
MA re-
mote con-
troller
(MA)
No ac-
knowl-
edgement
(ACK) at
IC trans-
mission to
LC
(1)
The power source of LOSSNAY has been shut off.
Turn off the power
source of LOSSNAY
and turn it on again.
If the error is accidental,
it will run normally.
If not, check the causes
(1) - (5).
(2)
When the address of LOSSNAY is changed in the
middle of the operation
(3)
Faulty or disconnected transmission wiring of
LOSSNAY
(4)
Disconnected connector (CN1) on LOSSNAY
(5)
Controller failure of LOSSNAY
ME re-
mote
control-
ler (RC)
ME re-
mote con-
troller
(RC)
MA re-
mote con-
troller
(MA)
No ac-
knowl-
edgement
(ACK) at
IC trans-
mission to
RC
(1)
Faulty transmission wiring at IC unit side.
Turn off the power
source of the outdoor
unit for 5 minutes or
more, and turn it on
again.
If the error is accidental,
it will run normally.
If not, check the causes
(1) - (4).
(2)
Faulty wiring of the transmission line for ME remote
controller
(3)
When the address of ME remote controller is
changed in the middle of the operation
(4)
ME remote controller failure
Содержание CMB-PW202V-J
Страница 1: ...Service Handbook AIR CONDITIONERS MODEL CMB PW202V J ...
Страница 9: ...HWE09070 GB ...
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 28: ... II Restrictions 19 HWE09070 GB ...
Страница 31: ... 22 II Restrictions GB HWE09070 ...
Страница 36: ... 27 HWE09070 GB III WCB Components 1 WCB Components 29 2 Control Box of the WCB 30 3 WCB Circuit Board 31 ...
Страница 37: ... 28 ...
Страница 40: ... III WCB Components 31 HWE09070 GB 3 WCB Circuit Board SW1 SW2 SW5 SW6 SW4 ...
Страница 41: ... 32 III WCB Components GB HWE09070 ...
Страница 42: ... 33 HWE09070 GB IV Electrical Wiring Diagram 1 Electrical Wiring Diagram of the WCB 35 ...
Страница 43: ... 34 ...
Страница 45: ... 36 IV Electrical Wiring Diagram GB HWE09070 ...
Страница 46: ... 37 HWE09070 GB V Refrigerant Circuit 1 Refrigerant Circuit Diagram 39 2 Principal Parts and Functions 40 ...
Страница 47: ... 38 ...
Страница 51: ... 42 ...
Страница 61: ... 52 VI Control GB HWE09070 ...
Страница 63: ... 54 ...
Страница 73: ... 64 ...
Страница 108: ... 99 HWE09070 GB IX LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 101 ...
Страница 109: ... 100 ...