SYSTEM CONFIGURATION
U I A
System number 2
Parameter configuration
For systems with high temperature zone (example bathroom radiators) managed using a thermostat not supplied by Manufacturer, set the
HEATING compensation curve, parameter 0159, to a value so as to reach a suitable outlet temperature for radiators.
The mixed zone is managed according to the compensation curve set for parameter 0174.
* obligatory values for the present configuration
Description
Menu
Parameter
no.
Default
Write set value
UOM
Select system configuration
Enable zone management
NOT = Disabled
YES = Enabled
Mn01
016A
NOT
YES
-
System type (table 1)
Mn01
0101
0
2*
-
Mixing valve ZONE 1
Type of mixing valve
1= 0-10V
Mn01
012T
0-10
HEATING compensation curve ZONE 1
Enable compensation curve NOT = Disabled YES = Enabled
Mn01
0167
NOT
Heating compensation curve number
Mn01
0174
0,7
Enable room temperature influence
NOT = Disabled
YES = Enabled
Mn01
0178
NOT
Room Authority
Mn01
0179
30
%
MINIMUM set point limit for curve
Mn01
0180
23
°C
MAXIMUM set point limit for curve
Mn01
0181
45
°C
COOLING compensation curve ZONE 1
Enable compensation curve NOT = Disabled YES = Enabled
Mn01
0169
NOT
Maximum temperature set point limit in cooling mode (Tm1)
Mn01
0132
20
°C
Minimum outside temperature corresponding to max. outlet
temperature (Te1)
Mn01
0133
23
°C
Minimum temperature set point limit in cooling mode (Tm2)
Mn01
0134
18
°C
Maximum outside temperature corresponding to min. outlet
temperature (Te2)
Mn01
0135
36
°C
HUMIDITY CONTROL ZONE 1
Enable compensation for room humidity, ZONE LT1
NOT = Disabled
YES = Enabled
Mn01
0171
NOT
Room relative humidity value to start increasing water temperature
set point
Mn01
0172
70
%
Maximum temperature hysteresis corresponding to 100%
relative humidity
Mn01
0173
15
°C
Enable contact HL1 as DEHUMIDIFIER (The contact closes and the
dehumidifier is activated when the humidity measured by the probe
on the A5 room controller exceeds the value set for parameter 0172)
Mn01
015A
DEHUMIDIFIER
HEATING compensation curve for HEAT PUMP MODE (THE TEMPERATURES MUST DIFFER FROM THOSE IN ZONE 1 & 2 BY AT
LEAST +3°C IN HEATING AND -3°C IN COOLING)
Enable compensation curve NOT = Disabled YES = Enabled
Mn01
0152
NOT
-
Compensation curve number
Mn01
0159
1
-
Enable room temperature influence
NOT = Disabled
YES = Enabled
Mn01
0163
NOT
-
Room Authority
Mn01
0164
30
%
MINIMUM set point limit curve
Mn01
0165
30
°C
MAXIMUM set point limit curve
Mn01
0166
48
°C
COOLING compensation curve for HEAT PUMP MODE (THE TEMPERATURES MUST DIFFER FROM THOSE IN ZONE 1 & 2 BY AT
LEAST +3°C IN HEATING AND -3°C IN COOLING)
Enable compensation curve NOT = Disabled YES = Enabled
Mn01
0154
NOT
-
Maximum temperature set point limit in cooling mode (Tm1)
Mn01
0128
20
°C
Minimum outside temperature corresponding to max. outlet
temperature (Te1)
Mn01
0129
23
°C
Minimum temperature set point limit in cooling mode (Tm2)
Mn01
0130
18
°C
Maximum outside temperature corresponding to min. outlet
temperature (Te2)
Mn01
0131
36
°C
Device address setting
ZONE 1 Room control unit address setting
addr
1
14
i-BX-(Y)_i-BX-N-(Y)
EN
68