i-BX-(Y)_i-BX-N-(Y)
CONTROL AND OPERATING CHARACTERISTICS
A
Description
MINIMUM set point limit for
SYSTEM curve
MAXIMUM set point limit for
SYSTEM curve
MINIMUM set point limit for com-
pensation curve in zone LT1
MAXIMUM set point limit for com-
pensation curve in zone LT1
Menu
Mn01
Mn01
Mn01
Mn01
Parameter
no.
0165
0166
0180
0181
Default
30
48
23
45
UOM
°C
°C
°C
°C
C) System water temperature limits in HEATING*
These define the temperature limits (minimum and maxi-
mum) that can be requested from the circuit and never
exceeded.
In the figure the minimum limit is 30°C and the maximum is
40°.
Between 30 and 40°C the water temperature will be able to
vary based on the trend in outside temperature.
For systems configured with mixed zones, the limits for the
SYSTEM curve and ZONE curve must be selected.
B) Room temperature influence in HEATING*
Function only active if the N-THC room control units (acces-
sory) are installed.
The compensation curve determines the heating water tem-
perature; this may then be corrected based on the difference
between the desired room set point and the actual room tem-
perature.
The correction made to the water temperature depends on
the “Room Authority” coefficient.
The higher the value of the Room Authority the higher the
correction to the system water temperature, and vice-versa.
This allows the water temperature to adapt quickly to
changes in the conditions inside the room.
The function can only be ENABLED if the A5 room controller
is positioned in the room and used to measure the reference
temperature.
Set authority values for the SYSTEM equal to or greater than
those for zones LT1.
Enabling room temperature influence on SYSTEM deviates
the calculated heat pump water temperature set point.
Enabling room temperature influence on ZONE LT1, deviates
the calculated water temperature set point to the system,
controlled by the mixing valve.
-2.5
-40
-30
-20
-10
0
10
20
30
40
50
60
2
-1,5
-1
-0,5
0
0,5
1
1,5
2
DT (Room temperature °C - Room set point °C)
System or zone water temperature deviation (°C)
Example referred to compensation curve 1.0
10 %
25 %
50 %
75 %
99 %
Set point with room temp. 20°C
Outside temp. (mean) (°C)
20
10
20
30
40
50
60
70
80
90
100
15
10
5
0
-5
-10
-15
-20
-25
-30
W
ater temp. (°C)
Description
Enable room temperature influ-
ence on SYSTEM
NOT
YES
SYSTEM Room Authority
Enable Room temperature influ-
ence on LT1
NOT
YES
LT1 Room Authority
Menu
Mn01
Mn01
Mn01
Mn01
Parameter
no.
0163
0164
0178
0179
Default
NOT
30
NOT
30
UOM
%
%
* the N-THC zone room control unit must be installed.
* the N-THC zone room control unit must be installed.