i-BX-(Y)_i-BX-N-(Y)
Contact closed = cooling operating mode signal
Contact open = heating operating mode signal
The “cooling/heating signal” must be configured for only
one of the configurable contacts listed.
INSTALLER CONNECTIONS
I A
25 27
SA2
SA1 Remote ON/OFF
The unit can be switched on/off from a remote control unit,
for example a timer or room thermostat.
The remote off function stops the compressor, fan and
pumps, while frost protection remains active.
- The unit can be switched on/off from contact SA1 only
when the unit has been switched on using the button on
the unit.
Set the following parameters:
Contact closed = Heat pump ON
Contact open = Heat pump OFF
25 26
SA1
Contact SA8 configured as “cooling/heating signal”:
Description
Enable contact as:
- BOILER SYSTEM
- SUMMER/WINTER
Menu
Mn01
Parameter
no.
015C
Value to be
set
SUMMER
WINTER
UOM
-
Contact SA9 configured as “cooling/heating signal”:
Description
Enable contact as:
- DHW RECIRCULATION
- DEHUMIDIFIER
- AT1 PUMP
- SUMMER/WINTER
Menu
Mn01
Parameter
no.
011B
Value to be
set
SUMMER/
WINTER
UOM
-
Description
Enable contact as:
- REMOTE ON/OFF
- BOILER BACkUP
Menu
Mn01
Parameter
no.
019A
Value to be
set
REMOTE
ON/OFF
UOM
-
SA2 Remote cooling/heating
Cooling/heating operating mode can be managed from a
remote control unit.
If remote cooling/heating changeover is enabled, the operat-
ing mode cannot be changed on the keypad.
Set the following parameters:
Contact closed = Cooling
Contact open = Heating
CAUTION: TURN OFF THE HEAT PUMP BEFORE
SWITCHING THE OPERATING MODE.
Description
Enable remote contact
- FROM kEYPAD
- FROM DIGITAL INPUT
Enable contact as:
- SUMMER/WINTER
- BOILER BACkUP
Menu
Mn01
Mn01
Parameter
no.
0100
019B
Value to be
set
FROM
DIGITAL
INPUT
SUMMER/
WINTER
UOM
-
-
Содержание Climaveneta i-BX 010-035T