57
EN
i-BX-(Y)_i-BX-N-(Y)
U I A
INSTALLATION AND CONNECTION OF N-THC ROOM CONTROL UNITS
• Close the cover A1 and secure it with the screw A2
• Plug in the 4-pin connector, figure
(7)
• Replace the terminal, starting with the lower tabs, applying
a hinge movement. Make sure that the electrical wires are
inside to ensure correct fastening (click on).
• Dimensions of A5 room controller figure
(8)
.
68
8
28
143
Wall
7
8
x3 sec.
• Main display
• Press the
+
buttons together for 3
seconds
• Turn the knob and select the password
(as shown in the table)
1
2
3
• Press the
button to exit the programming
procedure
7
4
5
6
A
B
• Press the knob to confirm
• Press the knob
A
Turn the knob to select the value
B
Press the knob to confirm
N-THC room control unit address setting procedure
System type
Address
Description
1 high temperature zone
(HT1)
11
High temperature zone room
control unit
1 low temperature zone (LT1)
14
Low temperature zone room
control unit
1 zone LT1 + 1 zone HT1
14
Low temperature zone room
control unit
11
High temperature zone room
control unit
Room control unit address by system type