MEES19K187
PQH
Y
-P
-T
(S)
L
MU-
A
1,
Y(S
)L
M
U-
A
1
44
2. EXTERNAL DIMENSIONS
WY-Series
PQHY-P144, 168, 192, 216, 240YSLMU-A1
Unit: mm(in)
b
e
a
c
d
T
o
indoor unit
Heat Source unit 1
Heat Source unit 2
T
o
indoor unit
Gas
T
winning pipe <optional parts>
f
Liquid
T
winning pipe <optional parts>
Note 1.Connect the pipes as shown in the figure above. Refer to the table below for the pipe size.
2.T
winning pipe should not be tilted more than 15 degrees from the horizontal plane.
3.See the Installation Manual for the details of
T
winning pipe installation.
4.The pipe section before the
T
winning pipe (sections "a" and "b" in the figure) must have at least 500mm(19-1
1
/16) of
straight section
(*including the straight pipe that is supplied with the
T
winning pipe).
5.Only use the
T
winning pipe by Mitsubishi (optional parts).
Twinning pipe connection size
Package unit name
Component unit name
Heat Source unit 1
T
w
inning pipe Kit(optional parts)
Heat Source unit 2
PQHY
-P144YSLMU-A1
PQHY
-P72YLMU-A1
CMY
-Y100CBK3
Indoor unit~T
winning pipe
Lquid
Gas
a
ø28.58(1-1/8)
b
PQHY
-P72YLMU-A1
PQHY
-P168YSLMU-A1
PQHY
-P96YLMU-A1
PQHY
-P72YLMU-A1
PQHY
-P192YSLMU-A1
PQHY
-P96YLMU-A1
PQHY
-P96YLMU-A1
PQHY
-P216YSLMU-A1
PQHY
-P120YLMU-A1
PQHY
-P96YLMU-A1
PQHY
-P240YSLMU-A1
PQHY
-P120YLMU-A1
PQHY
-P120YLMU-A1
ø15.88(5/8)
T
w
inning pipe~Heat Source unit 1
Lquid
Gas
c
d
T
w
inning pipe~Heat Source unit 2
Lquid
Gas
e
f
ø12.7(1/2)
ø19.05(3/4)
ø19.05(3/4)
ø9.52(3/8)
ø9.52(3/8)
ø22.2(7/8)
ø22.2(7/8)
ø12.7(1/2)
ø12.7(1/2)
20(13/16)
880(34-1
1/16)
880(34-1
1
/16)
1100(43-5/16)
550(21-1
1/16)
1780(70-1/8)
0000005752.BOOK 44 ページ 2020年2月28日 金曜日 午前10時8分