![Mitsubishi Electric CITY MULTI Скачать руководство пользователя страница 347](http://html.mh-extra.com/html/mitsubishi-electric/city-multi/city-multi_data-book_237998347.webp)
MEES19K187
PQ
HY-P-T
(S)L
MU-A
1, Y(S)L
M
U-A
1, Z(
S)
LMU
-A1
336
1. Piping Design
A
B
C
D
e
a
b
c
d
Indoor 1: P48
A:
40 m
a:
10 m
2: P36
B:
10 m
b:
5 m
3: P24
15 m
c:
10 m
4: P12
10 m
d:
10 m
5: P24
e:
10 m
The total length of liquid pipe of each size is as follows:
12.7 : A = 40 = 40 m
9.52 : B + C + D + a + b + c + e = 10 + 15 + 10 + 10 + 5 + 10 + 10 = 70 m
6.35 : d = 10 = 10 m
Example: PQHY-P144ZLMU
P24
P36
P48
P12
P24
=
+
+
+
+
+ 124
+
+
+
+
+ 124
(oz)
0 (ft.) x 2.80 (oz/ft.)
Additional
refrigerant charge
=
0 0
131
x 1.19 225
x 0.59 32
x 0.23
= 420 [oz]
Total length of liquid
x 2.80 (oz/ft.)
0 (ft.) x 1.94 (oz/ft.)
Total length of liquid
x 1.94 (oz/ft.)
131 (ft.) x 1.19 (oz/ft.)
Total length of liquid
x 1.19 (oz/ft.)
225 (ft.) x 0.59 (oz/ft.)
Total length of liquid
x 0.59 (oz/ft.)
32 (ft.) x 0.23 (oz/ft.)
Total length of liquid
x 0.23 (oz/ft.)
=
+
+
+
+
+ 3.5
+
+
+
+
+ 3.5
(kg)
0 (m) x 0.26 (kg/m)
Additional
refrigerant charge
=
0 0
40
x 0.11 70
x 0.054
10
x 0.021
= 11.9 kg
Total length of liquid
x 0.26 (kg/m)
0 (m) x 0.18 (kg/m)
Total length of liquid
x 0.18 (kg/m)
40 (m) x 0.11 (kg/m)
Total length of liquid
x 0.11 (kg/m)
70 (m) x 0.054 (kg/m)
Total length of liquid
x 0.054 (kg/m)
10 (m) x 0.021 (kg/m)
Total length of liquid
x 0.021 (kg/m)
m [kg]
m [kg]
ft. [oz]
ft. [oz]
or
Total capacity of connecting Indoor units Pt :
Pt = P48 + P36 + P24 + P12 + P24 = P144, therefore = 3.5kg
Indoor 1: P48
A:
131ft.
32ft.
2: P36
B:
32ft.
b:
16ft.
3: P24
C:
49ft.
c: 32ft.
4: P12
D:
32ft.
d:
32ft.
5: P24
e:
32ft.
The total length of liquid pipe of each line is as follows:
Total capacity of connecting Indoor units Pt :
A = 131 = 131ft.
B + C + D + a + b + c + e = 32 + 49 + 32 + 32 + 16 + 32 + 32 = 225ft.
d = 32 = 32ft.
Pt = P48 + P36 + P24 + P12 + P24 = P144, therefore = 124oz
The above calculation result of the amount of refrigerant to be charged must become below the value in the table below.
Limitation of the amount of refrigerant to be charged
Total index of the heat source units
P72
P96
P120
P144
P168
ZLMU
ZLMU
ZLMU
ZLMU
ZLMU
Maximum refrigerant charge
Factory charged
11 lbs
1 oz
11 lbs
1 oz
11 lbs
1 oz
13 lbs
4 oz
13 lbs
4 oz
Charged on site
48 lbs
9 oz
62 lbs
14 oz
65 lbs
1 oz
92 lbs
10 oz
113 lbs
9 oz
Total for system
59 lbs
9 oz
73 lbs
14 oz
76 lbs
1 oz
105 lbs
14 oz
126 lbs
13 oz
26 lbs
8 oz
148 lbs
13 oz
175 lbs
5 oz
26 lbs
8 oz
154 lbs
6 oz
180 lbs
13 oz
Factory charged
5.0kg
5.0kg
5.0kg
6.0kg
6.0kg
Charged on site
22.0kg
28.5kg
29.5kg
42.0kg
51.5kg
Total for system
27.0kg
33.5kg
34.5kg
48.0kg
57.5kg
P192
ZLMU
13 lbs
4 oz
118 lbs
0 oz
131 lbs
3 oz
6.0kg
53.5kg
59.5kg
P168
ZSLMU
22 lbs
1 oz
113 lbs
9 oz
135 lbs
10 oz
P144
ZSLMU
22 lbs
1 oz
92 lbs
10 oz
114 lbs
11 oz
10.0kg
51.5kg
61.5kg
10.0kg
42.0kg
52.0kg
Total index of the heat source units
Maximum refrigerant charge
Factory charged
Charged on site
Total for system
P336
ZSLMU
P360
ZSLMU
Factory charged
Charged on site
Total for system
12.0kg
67.5kg
79.5kg
26 lbs
8 oz
148 lbs
13 oz
175 lbs
5 oz
26 lbs
8 oz
148 lbs
13 oz
175 lbs
5 oz
P288
ZSLMU
P312
ZSLMU
12.0kg
67.5kg
79.5kg
12.0kg
67.5kg
79.5kg
22 lbs
1 oz
121 lbs
5 oz
143 lbs
5 oz
22 lbs
1 oz
118 lbs
0 oz
140 lbs
0 oz
P216
ZSLMU
P192
ZSLMU
10.0kg
55.0kg
65.0kg
10.0kg
53.5kg
63.5kg
22 lbs
1 oz
123 lbs
8 oz
145 lbs
9 oz
P240
ZSLMU
10.0kg
56.0kg
66.0kg
12.0kg
70.0kg
82.0kg