MEES19K187
PQRY-
P
-T(
S
)LMU
-A1, Y(
S)LMU
-A1
198
2. EXTERNAL DIMENSIONS
WR2-Series
2. EXTERNAL DIMENSIONS
PQRY-P72, 96, 120TLMU-A1
Unit: mm(in)
<Accessories>
• Refrigerant (low pressure) conn. elbow
• • • • •
1pc.
(P72/P96/P120 ; Packaged in the accessory kit)
(P72/P96/P120 ; Packaged in the accessory kit)
• Sealing material for field piping (high pressure, low pressure)
• • • • •
1pc. each
(P72/P96/P120 ; Packaged in the accessory kit)
Note1.Close a hole of the water piping, the refrigerant piping,
the power supply
, and the control wiring and unused knockout
holes with the putty etc. so as not to infiltrate rain water
etc.(field erection work)
Note2.At the time of product shipment, the front side piping
specification serves as the local drainage connection.
When connecting on the rear side, please remove the
rear side plug sealing corks, and attach a front side.
Ensure there is no leak after the attachment has been fitted.
Note3.T
ake notice of service space as Fig.A. (In case of single
installation, 600mm(23-5/8) or more of back space as front space
makes easier access when servicing the unit from rear side.)
Note4.If water pipes or refrigerant pipes stretch upward,
required space for service and maintenance due to
replacement of control box is shown in Fig.B.
Note5.Environmental condition for installation; -20~40°C(DB) (-4~104°F)
as indoor installation.
Note7.Ensure that the drain piping is downward with a pitch of
more than 1/100.
Note8.At brazing of pipes, wrap the refrigerant service valve
with wet cloth and keep the temperature of
refrigerant service valve under 120°C(248°F).
(P72/P96/P120 ; Packaged in the accessory kit)
• Pipe cover for low pressure
• • • • •
1pc.
(P72/P96/P120 ; Packaged in the accessory kit)
• Sealing material for drain socket
• • • • •
1pc.
• Sealing material for water stopper
• • • • •
1pc.
• W
a
ter stopper
• • • • •
1pc.
(P72/P96/P120 ; Packaged in the accessory kit)
(5/8)
(3/4)
ø19.05 Brazed
ø15.88 Brazed
Low pressure
High pressure
Low pressure
High pressure
Diameter
PQR
Y-P120TLMU-A1
PQR
Y-P96TLMU-A1
PQR
Y-P72TLMU-A1
Model
Connecting pipe specifications
(1)
ø25.4
Refrigerant pipe
Service valve
(3/4)
ø19.05
*1 *2
*2.Use the pipe joint(field supply) and connect to the refrigerant service valve piping.
*1.Connect by using the connecting pipes and elbow that are supplied.
*1 *2
(3/4)
(7/8)
ø22.2 Brazed
ø19.05 Brazed
*1
*1 *2
1100(43-5/16)
435(17-3/16)
23(15/16)
124(4-15/16)
208
394(15-9/16)
422(16-5/8)
58(2-5/16)
570(22-1/2)
185(7-5/16)
(8-1/4)
77(3-1/16)
140(5-9/16)
75(3)
83(3-5/16)
(8-9/16)
29
(1-3/16)
91
(3-5/8)
77(3-1/16)
216
145(5-3/4)
89(3-9/16)
880(34-1
1/16)
550(21-11/16)
721 (28-7/16)
473(470~476)
31.5
31.5
(1-1/4)
(18-5/8)(18-9/16~18-3/4)
(1-1/4)
(2-7/8)
(2-7/8)
72.5
72.5
2×2-14(9/16)×31(1-1/4) Oval hole
(Mounting pitch)
(Mounting pitch)
(536)(21-1/8)
(866)(34-1/8)
Bottom view
600(23-5/8)
450(17-3/4)
163(6-7/16)
(503)
1100(43-5/16)
350(13-13/16)
(90)
700
(90)
(34-1
1/16)
880
450(17-3/4)
163(6-7/16)
600(23-5/8)
(19-13/16)
(3-9/16)
(3-9/16)
(27-9/16)
(21-1/8)
536
Control box
Refrigerant service valve <High pressure>
Refrigerant service
valve <Low pressure>
Service panel
Top view
(front side)
Service space
(front side)
Service space
control box
The space for
replacement
control box
The space for
replacement
T
op view
Front view
Right side view
Back view
Fig.B
Fig.A
7
6
1
5
4
3
8
2
8
NO.
For pipes
For wires
For transmission
cables
Usage
Front through hole
Front through hole
Front through hole
Front through hole
Specifications
Rc3/4 Screw
NPT1-1/2
Screw
NPT1-1/2
Screw
inlet
outlet
Drain pipe
W
a
ter pipe
1
2
4
3
5
6
7
8
140 × 77 Knockout hole
(5-9/16) (3-1/16)
ø62.7 or ø34.5 Knockout hole
(2-1/2) (1-3/8)
ø43.7 or ø22.2 Knockout hole
(1-3/4) (7/8)
ø
45 Knockout hole
(1-13/16)
ø
34 Knockout hole
(1-3/8)
(Uses when twinning kit (optional parts) is mounted.)
Front through hole
• Refrigerant (high pressure) conn. pipe
• • • • •
1pc.
(P72/P96/P120 ; Packaged in the accessory kit)
Note6.In case the temperature around the heat source unit has
possibility to drop under 0°C(32°F) or the inlet-water temp.
drops under 10°C(50°F), be careful for the following
point to prevent the pipe burst by the water pipe freeze-up.
•Add brine to water circuit.
•Circulate the water all the time even if the heat source
unit is not in operation.
•Drain the water from inside of the heat source unit when
the heat source unit will not operate for a long term.
0000005754.BOOK 198 ページ 2020年2月28日 金曜日 午後12時2分