13.5. Humidifier
Humidifier Control
Sequence of operation:
1. The humidistat closes CNF
2. The fan starts on high
3. CN25 provides 12VDC to turn on the Humidifier
(do not exceed 1 Watt draw per relay)
4. When the Humidistat opens, the fan continues to run for
30 seconds to clear the ductwork of moist air
5. If defrost starts during humidifier operation
CN25 de-energizes
Humidistat:
Non-Voltage a-contact input
Contact rating voltage >=15VDC
Contact Rating Current > = 0.1 A
Minimum Applicable Load =< 1mA at DC
Dip Switch
Setting
Humidistat Output
Condition
(No Defrost/No Error)
CN25 Output
Fan Speed
SW1-6
CNF Input
OFF*
OFF
Heat operation & Thermo OFF
OFF
RC setting
Heat operation & Thermo ON
ON
Heat operation & Thermo OFF
OFF
RC setting
Heat operation & Thermo ON
ON
High
ON
OFF
Heat operation & Thermo OFF
OFF
RC setting
Heat operation & Thermo ON
ON
Heat operation & Thermo OFF
ON
High
Heat operation & Thermo ON
-
-
Except for heat operation
OFF
RC setting
RC: Remote controller
The fan continues to run for 30 seconds after the humidifier stops.
*Factory Setting
max 30 ft.