Module :

 

PUHY-P216TSKMU-A – DIMENSIONS

ø28.58(1-1/8)

ø15.88(5/8)

CMY

-Y100CBK3

PUHY

-P96TKMU-A(-BS)

PUHY

-P120TKMU-A(-BS)

PUHY

-P216TSKMU-A(-BS)

b

a

Gas

Liquid

Outdoor unit 2

Outdoor unit 1

Indoor unit~T

winning pipe

Outdoor 

Twinning Kit(optional parts)

Component unit name

Package unit name

Twinning pipe connection size

Note 

1.Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.

 

2.T

winning pipes should not be tilted more than 15 degrees from the horizontal plane.  

 

   Be sure to see the Installation Manual for details of 

Twinning pipe installation.

 

3.The pipe section before the 

Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm(19-1

1/16) of straigh

t section 

 

   (*including the straight pipe that is supplied with the 

Twinning pipe).

 

4.Only use the 

Twinning pipe by Mitsubishi (optional parts).

d or f

c or e

Gas

Liquid

P96 P120

Unit model

Twinning pipe~Outdoor unit

Front view

Left view

To indoor unit

Liquid 

Twinning pipe<optional parts>

Gas 

Twinning pipe<optional parts>

To indoor unit

Outdoor unit 2

Outdoor unit 1

Discharge air

Intake air

Intake air

Intake air

ø28.58(1-1/8)

ø22.2(7/8)

ø12.7(1/2)

ø9.52(3/8)

d

f

b

a

e

c

30(1-3/16)

1750(68-29/32)

1650(64-31/32)

740(29-5/32)

1220(48-1/16)

PUHY-P216TSKMU-A(-BS)

Unit : mm(in.)

Содержание City Multi PUHY-P120TKMU-A

Страница 1: ...stem Data Heating Power Input kW 19 26 Cooling Current 208 230V R L A 52 1 47 1 Refer to System Data Heating Current 208 230V R L A 59 4 53 7 Minimum Circuit Ampacity MCA A Refer to Module Data 45 42 34 31 Maximum Breaker Size A Refer to Module Data 50 40 Maximum Overcurrent Protection A Refer to Module Data 73 67 57 52 Piping Diameter Refer to System Data From Twinning Kit to Indoor Units Brazed ...

Страница 2: ...anual for details of Twinning pipe installation 3 The pipe section before the Twinning pipe sections a and b in the figure must have at least 500mm 19 11 16 of straight section including the straight pipe that is supplied with the Twinning pipe 4 Only use the Twinning pipe by Mitsubishi optional parts d or f c or e Gas Liquid P96 P120 Unit model Twinning pipe Outdoor unit Front view Left view To i...

Страница 3: ...ic fan guard for snow hood attachment Snow hood attachment hole Refrigerant service valve gas Refrigerant service valve liquid 6 25 32 8 25 32 ø34 Knockout hole ø52 Knockout hole ø65 Knockout hole ø43 7 or ø22 2 Knockout hole ø62 7 or ø34 5 Knockout hole 150 94 Knockout hole 140 77 Knockout hole Specifications For transmission cables For pipes Bottom through hole Front through hole Usage For wires...

Страница 4: ...ttachment Intake air Discharge air Refrigerant service valve gas Refrigerant service valve liquid Control box Intake air Service panel Intake air Sling hole 2 5 2X2 14 9 16 X20 13 16 Oval hole 2X2 80 3 5 32 X35 1 13 32 Oval hole 6 ø34 Knockout hole ø52 Knockout hole ø65 Knockout hole ø43 7 or ø22 2 Knockout hole ø62 7 or ø34 5 Knockout hole 150 94 Knockout hole 140 77 Knockout hole Specifications ...

Страница 5: ...ronmental protection set by the International Standard Organization ISO Twinning Kit CMY Y100CBK3 1 15 16 2 pcs 2 pcs 3 7 8 9 1 2 7 7 32 3 9 32 19 29 32 13 15 32 23 5 32 6 5 16 2 15 32 1 15 16 2 15 32 Distributer Distributer Pipe cover Dot dashed part 1 2 1 2 1 2 1 2 Local brazing Note 2 5 8 5 8 1 1 8 Note 2 1 7 8 1 7 8 Pipe cover Dot dashed part Local brazing 1 1 8 2 pcs 7 8 3 4 1 2 5 8 1 2 3 8 1...

Отзывы: