Module :
PUHY-P216TSKMU-A – DIMENSIONS
ø28.58(1-1/8)
ø15.88(5/8)
CMY
-Y100CBK3
PUHY
-P96TKMU-A(-BS)
PUHY
-P120TKMU-A(-BS)
PUHY
-P216TSKMU-A(-BS)
b
a
Gas
Liquid
Outdoor unit 2
Outdoor unit 1
Indoor unit~T
winning pipe
Outdoor
Twinning Kit(optional parts)
Component unit name
Package unit name
Twinning pipe connection size
Note
1.Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2.T
winning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of
Twinning pipe installation.
3.The pipe section before the
Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm(19-1
1/16) of straigh
t section
(*including the straight pipe that is supplied with the
Twinning pipe).
4.Only use the
Twinning pipe by Mitsubishi (optional parts).
d or f
c or e
Gas
Liquid
P96 P120
Unit model
Twinning pipe~Outdoor unit
Front view
Left view
To indoor unit
Liquid
Twinning pipe<optional parts>
Gas
Twinning pipe<optional parts>
To indoor unit
Outdoor unit 2
Outdoor unit 1
Discharge air
Intake air
Intake air
Intake air
ø28.58(1-1/8)
ø22.2(7/8)
ø12.7(1/2)
ø9.52(3/8)
d
f
b
a
e
c
30(1-3/16)
1750(68-29/32)
1650(64-31/32)
740(29-5/32)
1220(48-1/16)
PUHY-P216TSKMU-A(-BS)
Unit : mm(in.)