background image

Job Name: 

Location:

Engineer Name:

 

Contractor:

System No.: 

Date:

Model:

 

PUHY-P216TSKMU-A

(Consists of One PUHY-P120TKMU-A, One PUHY-P96TKMU-A, and One CMY-Y100CBK3 Twinning Kit)

OUTDOOR VRF HEAT PUMP SYSTEM FEATURES

• 

3-phase, 208/230V

• 

Modular variable refrigerant flow (VRF) systems;

 

  smaller capacity units can be piped together to form a single, 

  large-capacity two-pipe system

• Required

 T

winning Kit allows for easy field piping connection

• Selectable fan static, 0.12 or 0.24"WG external static pressure;

 

  factory set to 0"WG

• Connects to CIT

Y MUL

TI indoor units; controlled via 

 

  CIT

Y MUL

TI Controls Network (CMCN)

• External finish: Pre-coated Galvanized-steel Sheets

• Operating

 T

emperature Range

 

 

Cooling (Outdoor): 23° ~ 115°F (-5° ~ +46°C) DB

 

Heating (Outdoor): -4° ~ +60°F (-20° ~ +16°C) WB

OPTIONAL PARTS

 T

w

inning 

K

it*.…………………………………...…….CMY-Y

1

00C

BK

3

 T-

B

ranch Joint 

(≤

 72,000 

B

tu/h

)

………………..........CMY-Y

1

02SS

-G2

 T-

B

ranch Joint 

(≤

 

144

,000 

B

tu/h

)

……………….…....CMY-Y

1

02

LS-G2

 T-

B

ranch Joint 

(≤

 23

4

,000 

B

tu/h

)

……………….........CMY-Y202

S-G2

 Header 

(4

-

B

ranch

;

 

 72,000 

B

tu/h

)

........………………CMY-Y

1

0

4C-G

 Header 

(

8-

B

ranch

;

 

 

144

,000 

B

tu/h

)

......………………CMY-Y

1

0

8C-G

 Header 

(1

0-

B

ranch

;

 

 23

4

,000 

B

tu/h

)

....………………CMY-Y

1

0

10C-G

* T

w

inning 

K

it is necessary to combine the refrigerant 

o

w

s of the  

   modules and is sold separately.

Specifications

System 

Module 1 

Module 2

Unit 

Type

PUHY

-P216TSKMU-A

PUHY

-P120TKMU-A

PUHY

-P96TKMU-A

Nominal Cooling Capacit

y

Btu/h

216,000

120,000

96,000

Nominal Heating Capacit

y

Btu/h

243,000

135,000

108,000

External Dimensions (H x W x D

)

In. / mm

Refer to Module Data

65

 

x

 

6

8-29/32 

x

 29-

5

/23  /

1

,

65

x

 

1

,7

5

x

 7

4

0

65

 

x

 

48

8

-1/16 x 29-5/32  / 

 

1

,

65

x

 

1

,220  

x

 7

4

0

Net Weight

Lbs. / kg

1,220 / 557

697 / 316

532 / 241

Electrical Power Requirements

V

oltage, Phase, Hertz

R

efer to Module Data**

208 / 230V

, 3-phase, 60Hz**

Cooling Power Input

kW

16.90

Refer to System Data

Heating Power Input

kW

19.26

Cooling Current (208/230V

)

R.L.A.

52.1 / 47.1

Refer to System Data

Heating Current (208/230V

)

R.L.A.

59.4 / 53.7

Minimum Circuit

 

Ampacity

 

(MCA)**

A

R

efer to Module Data**

45 / 42**

34 / 31**

Maximum Breaker Size**

A

R

efer to Module Data**

50**

40**

Maximum Overcurrent Protection**

A

R

efer to Module Data**

73 / 67**

57 / 52**

Piping Diameter

Refer to System Data

F

rom

 T

w

i

nn

i

ng

 

K

i

t

 

to

 I

ndoor

 U

n

i

ts 

(

B

raz

e

d

(

I

n.

 

/

 

mm

)

Liquid (High Pressure)

5/8 / 15.88

Gas (Low Pressure)

1-1/8 / 28.58

From Modules to 

T

winning Kit 

(Brazed) (In. / mm)

Liquid (High Pressure)

Refer to Module Data

1/2 / 12.7

3/8 / 9.52

Gas (Low Pressure)

1-1/8 / 28.58

7/8 / 22.2

Indoor Unit

T

otal Capacity

50 to 130% of ODUs

Refer to System Data

Model / Quantity

P06 ~ P96 / 2 to 46

Sound Pressure Levels

dB(A)

62.5

60.0

58.0

Fan

Refer to Module Data

T

ype x Quantity

Propeller Fan x 2

Propeller Fan x 1

Airflow Rate

CFM

11,300

6,200

Di

r

ec

t

-

dr

i

v

e I

nv

e

rt

e

r

 M

otor

 O

ut

p

ut

kW

0.92 + 0.92

0.92

Compressor Operating Range

8% to 100%

Refer to System Data

Compressor 

T

ype x Quantity

Refer to Module Data

Inverter-driven Scroll Hermetic x 1 Inverter-driven Scroll Hermetic x 1

Compressor Motor Output

kW

8.1

7.1

Compressor Crankcase Heater

kW

-

-

Refrigerant

Refer to Module Data

R410A

Lubricant

MEL32

High-pressure Protection Device

Refer to Module Data

601 psi / 4.15 MPa

601 psi / 4.15 MPa

Compressor / Fan Protection Device

O

verheat 

P

rotection / Thermal S

w

itch

O

verheat 

P

rotection / Thermal S

w

itch

Inverter Protection Device

Overheat / Overcurrent Protectio

n

Overheat / Overcurrent Protection

B

lu

e Fi

n

 A

nt

i-c

orros

i

on

 P

rot

ec

t

i

on

Cellulose- and polyurethane-resin coating treatment applied to condenser coil that protects it from air contaminants

 

≥1μ

m thic

k;

 Salt Spray Test Method - no unusual rust development to 

4

80 hours.

P

UHY-

P120TKMU-A

** Each individual module re

q

uires a separate electrical connection. 

R

eference electrical data for each individual module.

P

UHY-

P96TKMU-A

Содержание City Multi PUHY-P120TKMU-A

Страница 1: ...stem Data Heating Power Input kW 19 26 Cooling Current 208 230V R L A 52 1 47 1 Refer to System Data Heating Current 208 230V R L A 59 4 53 7 Minimum Circuit Ampacity MCA A Refer to Module Data 45 42 34 31 Maximum Breaker Size A Refer to Module Data 50 40 Maximum Overcurrent Protection A Refer to Module Data 73 67 57 52 Piping Diameter Refer to System Data From Twinning Kit to Indoor Units Brazed ...

Страница 2: ...anual for details of Twinning pipe installation 3 The pipe section before the Twinning pipe sections a and b in the figure must have at least 500mm 19 11 16 of straight section including the straight pipe that is supplied with the Twinning pipe 4 Only use the Twinning pipe by Mitsubishi optional parts d or f c or e Gas Liquid P96 P120 Unit model Twinning pipe Outdoor unit Front view Left view To i...

Страница 3: ...ic fan guard for snow hood attachment Snow hood attachment hole Refrigerant service valve gas Refrigerant service valve liquid 6 25 32 8 25 32 ø34 Knockout hole ø52 Knockout hole ø65 Knockout hole ø43 7 or ø22 2 Knockout hole ø62 7 or ø34 5 Knockout hole 150 94 Knockout hole 140 77 Knockout hole Specifications For transmission cables For pipes Bottom through hole Front through hole Usage For wires...

Страница 4: ...ttachment Intake air Discharge air Refrigerant service valve gas Refrigerant service valve liquid Control box Intake air Service panel Intake air Sling hole 2 5 2X2 14 9 16 X20 13 16 Oval hole 2X2 80 3 5 32 X35 1 13 32 Oval hole 6 ø34 Knockout hole ø52 Knockout hole ø65 Knockout hole ø43 7 or ø22 2 Knockout hole ø62 7 or ø34 5 Knockout hole 150 94 Knockout hole 140 77 Knockout hole Specifications ...

Страница 5: ...ronmental protection set by the International Standard Organization ISO Twinning Kit CMY Y100CBK3 1 15 16 2 pcs 2 pcs 3 7 8 9 1 2 7 7 32 3 9 32 19 29 32 13 15 32 23 5 32 6 5 16 2 15 32 1 15 16 2 15 32 Distributer Distributer Pipe cover Dot dashed part 1 2 1 2 1 2 1 2 Local brazing Note 2 5 8 5 8 1 1 8 Note 2 1 7 8 1 7 8 Pipe cover Dot dashed part Local brazing 1 1 8 2 pcs 7 8 3 4 1 2 5 8 1 2 3 8 1...

Отзывы: