![Mitsubishi Electric CITY MULTI PUHY-P-ZKMU-A Скачать руководство пользователя страница 5](http://html.mh-extra.com/html/mitsubishi-electric/city-multi-puhy-p-zkmu-a/city-multi-puhy-p-zkmu-a_installation-manual_1811755005.webp)
5
GB
6SHFL¿FDWLRQV
Model
PUHY-P72ZKMU-A(-BS)
PUHY-P96ZKMU-A(-BS)
PUHY-P120ZKMU-A(-BS)
PUHY-P144ZKMU-A(-BS)
PUHY-P168ZSKMU-A(-BS)
Sound level (60Hz)
58dB<A>
58dB<A>
60dB<A>
61dB<A>
61dB<A>
External static pressure
0 Pa
*2
Indoor units
Total capacity
50 ~ 130%
*1
Model
06 ~ 72
06 ~ 96
Quantity
1 ~ 15
1 ~ 20
1 ~ 26
1 ~ 31
1 ~ 36
Operation
temperature
Standard type
Cooling mode: – 5°CDB ~ 46°CDB [23°FDB ~ 115°FDB]
Heating mode: – 20°CWB ~ 15.5°CWB [– 4°FWB ~ 60°FWB]
Outside air
intake type
Cooling mode: 21°CDB/15.5°CWB ~ 46°CDB/35°CWB (70°FDB/60°FWB ~ 115°FDB/95°FWB)
Heating mode: – 10°CDB ~ 20°CDB [14°FDB ~ 68°FDB]
Model
PUHY-P192ZSKMU-A(-BS) PUHY-P216ZSKMU-A(-BS) PUHY-P240ZSKMU-A(-BS) PUHY-P264ZSKMU-A(-BS) PUHY-P288ZSKMU-A(-BS)
Sound level (60Hz)
62.5dB<A>
62.5dB<A>
63dB<A>
63.5dB<A>
64dB<A>
External static pressure
0 Pa
*2
Indoor units
Total capacity
50 ~ 130%
*1
Model
06 ~ 96
Quantity
1 ~ 41
2 ~ 46
2 ~ 50
2 ~ 50
2 ~ 50
Operation
temperature
Standard type
Cooling mode: – 5°CDB ~ 46°CDB [23°FDB ~ 115°FDB]
Heating mode: – 20°CWB ~ 15.5°CWB [– 4°FWB ~ 60°FWB]
Outside air
intake type
Cooling mode: 21°CDB/15.5°CWB ~ 46°CDB/35°CWB (70°FDB/60°FWB ~ 115°FDB/95°FWB)
Heating mode: – 10°CDB ~ 20°CDB [14°FDB ~ 68°FDB]
Model
PUHY-P312ZSKMU-A(-BS) PUHY-P336ZSKMU-A(-BS) PUHY-P360ZSKMU-A(-BS)
Sound level (60Hz)
64.5dB<A>
64.5dB<A>
65dB<A>
External static pressure
0 Pa
*2
Indoor units
Total capacity
50 ~ 130%
*1
Model
06 ~ 96
Quantity
2 ~ 50
2 ~ 50
2 ~ 50
Operation
temperature
Standard type
Cooling mode: – 5°CDB ~ 46°CDB [23°FDB ~ 115°FDB]
Heating mode: – 20°CWB ~ 15.5°CWB [– 4°FWB ~ 60°FWB]
Outside air
intake type
Cooling mode: 21°CDB/15.5°CWB ~ 46°CDB/35°CWB
(70°FDB/60°FWB ~ 115°FDB/95°FWB)
Heating mode: – 10°CDB ~ 20°CDB [14°FDB ~ 68°FDB]
*1: The total indoor capacity of units run simultaneously is 130% or less.
*2: To enable high static pressure, set the DipSW on the main panel as follows.
SW6-4: ON, SW6-5 60Pa compatible: OFF, 30Pa compatible: ON
5. Parts included list
Band
Model
P72
2 pcs.
P96
2 pcs.
P120
2 pcs.
P144
2 pcs.