When unit is surrounded by walls
C
B
A
B
650
325
A
C
H
h
Hh
D
E
<Side view>
A
L
1
or more
B
L
2
or more
C
Front
D
Front panel
E
Rear panel
Note:
•
Wall heights (H) of the front and the back sides shall be within
height of front panel and rear panel.
•
If the panel height is exceeded, add the “h” dimension of the
figure above to L
1
and L
2
in the table above.
Model
L
1
L
2
PUHY-P400
450
250
PUHY-P500
Example: When h is 100
The L
1
dimension becomes 450+100=550 mm.
When there is an obstruction above the unit
A
E
D
C
F
B
When there is little space
up to an obstruction
A
45
°
or more
B
300 mm or more
C
Front
D
1000 mm or more
E
Air outlet guide (Procured at the site)
F
Rear
6.2. Collective installation and continu-
ous installation
Space required for collective installation and continuous installation:
When installing several units, leave the space between each block as
shown below considering passage for air and people.
B
C
C
D
A
A
*
E
*
F
B
B
A
A
*
F
F
F
F
F
*
E
B
C
C
C
C
C
D
B
E
G
C
C
B
A
E
A
B
C
G
E
A
C
D
D
A
A
(Must be open)
B
Wall height (H)
C
Front
D
1000 mm or more
E
250 mm or more
F
450 mm or more
G
900 mm or more
Note:
•
Open in the two directions.
•
In case wall height (H) exceeds overall height of unit, add “h”
dimension (h=wall height <H> – overall height of unit) to * marked
dimension.
•
If there is a wall at both the front and the rear of the unit, install
up to three units consecutively in the side direction and provide
a space of 1000 mm or more as inlet space/passage space for
each three units.