MEES21K047
PQ
R
Y-
P-
Z(
S)
LM
U
-A
1
96
10. ELECTRICAL WORK
WR2-Series-575V
10-4. Power supply examples
The local standards and/or regulations is applicable at a higher priority.
10-4-2. PQRY-P144, 168, 192, 216, 240, 288, 312, 336ZSLMU
Power supply
Note4
Note3
Note3
To *1 or *2
*1
Connector
CN41 CN40
Power supply
1-phase
208-230V 60Hz
Note11
Central control
transmission cable
>=1.25mm
2
Shield cable
(CVVS, CPEVS
MVVS)
Indoor-heat source
transmission cable
>=1.25mm
2
Shield cable
(Using MA remote controller)
Connecting TB5 terminal.
G
G
TB7
(S)
TB7
(S)
TB1
(L1,L2,L3)
TB3
(M1,M2)
TB7
(M1,M2)
TB3
(M1,M2)
TB7
(M1,M2)
SC
Note12
HU
Note4
To other HU
* Power supply
specifications vary with the
model of connected indoor
units or BC controller
<In the case a system controller is connected.>
TB1
(L1,L2,L3)
.
Note8
Power supply
1-phase
208-230V 60Hz
G
TB5
(M1,M2)
TB2
(L,N)
S
TB15
(1,2)
TB5
(M1,M2)
TB2
(L,N)
S
TB15
(1,2)
TB5
(M1,M2)
TB2
(L,N)
S
S
S
E
TB15
(1,2)
TB5
(M1,M2)
TB2
(L,N)
TB1
(R,S)
TB2 TB3
S
TB15
(1,2)
Transmission
booster
Note9
Note10
MA R/C
MA R/C
MA R/C
IU
(Shield)
(Shield)
(Shield)
(Shield)
(Shield)
(Shield)
Note7
Note8
Pull box
*2
Indoor-heat source
transmission cable
>=1.25mm
2
Shield cable
(Using ME remote controller)
Connecting TB5 terminal.
Power supply
1-phase
208-230V 60Hz
ME R/C
ME R/C
ME R/C
Note7
Note8
Note8
Power supply
1-phase
208-230V 60Hz
Note11
G
TB5
(M1,M2)
TB2
(L,N)
S
TB15
(1,2)
TB5
(M1,M2)
TB2
(L,N)
S
TB15
(1,2)
TB5
(M1,M2)
TB2
(L,N)
S
S
S
E
TB15
(1,2)
TB5
(M1,M2)
TB2
(L,N)
TB1
(R,S)
TB2 TB3
S
TB15
(1,2)
Transmission
booster
Note9
Note10
IU
(Shield)
(Shield)
(Shield)
(Shield)
(Shield)
(Shield)
* Power supply
specifications vary with the
model of connected indoor
units or BC controller
Pull box
BC controller(Main)
TB02
(M1,M2)
S
(Shield)
BC controller(Sub)
TB02
(M1,M2)
S
BC controller(Main)
TB02
(M1,M2)
S
(Shield)
BC controller(Sub)
TB02
(M1,M2)
S
TB01
L,N
TB01
L,N
TB01
L,N
TB01
L,N
3-phase 3-wire
575V 60Hz
Note11,13
Power supply
3-phase 3-wire
575V 60Hz
Note11,13
G
G
G
G
Breakers for
current leakage Switch
Breakers for
current leakage Switch
Breakers for
current leakage Switch
Breakers for
current leakage Switch
Breakers for
current leakage Switch
Breakers for
current leakage Switch
HU
MA R/C cable
0.3-1.25mm
2
<=200m
Note5, 6
ME R/C cable
0.3~1.25mm
2
<=10m
Note5, 6
Note:
1 The transmission cable is not-polarity double-wire.
2 Symbol means a screw terminal for wiring.
3 The shield wire of transmission cable should be connected to the grounding terminal at
Heat source unit. All shield wire of M-Net transmission cable among Indoor units should be
connected to the S terminal at Indoor unit or all shield wire should be connected
together.
The broken line at the scheme means shield wire.
4 When the Heat source unit connected with system controller, power-supply to TB7 of the
heat source unit(s) is needed. The connector change from CN41 to CN40 at one of the
heat source units will enable the heat source unit to supply power to TB7, or an extra power
supply unit PAC-SC51KUA should be used. The transmission cable (above 1.25mm
2
,
shielded, CVVS/CPEVS/MVVS) among Heat source units and system controllers is called
central control transmission cable. The shield wire of the central control transmission
cable must be grounded at the Heat source unit whose CN41 is changed to CN40.
When
the power supply unit PAC-SC51KUA is used, connect the shielded cable to the ground
terminal on the PAC-SC51KUA.
5 MA R/C transmission cable (0.3-1.25mm
2
) must be less than 200m in length, while ME
R/C transmission cable (0.3-1.25mm
2
) must be less than 10m in length. But transmission
cable to the ME R/C can be extend using a M-NET cable (>=1.25mm
2
) when the length
is counted in the M-Net length.
7 MA remote controller and ME remote controller should not be grouped together. When a
6 To wire PAR-CT01MAU, PAR-40MAAU, and PAC-YT53CRAU, use a wire with a diameter
8 If using 1 or 2 (main/sub) MA remote controller to control more than 1 Indoor unit, use MA
transmission cable to connect all the TB15 terminals of the Indoor units. It is called
of 0.3mm
2
[AWG 22].
"Grouping".
PAR-CT01MAU or PAR-40MAAU is connected to a group, no other MA remote controllers
can be connected to the same group.
If using 1 or 2 (main/sub) ME remote controller control more than 1 indoor unit, set
address to Indoor unit and ME remote controller. For the method, refer to 11-4. "Address
setting".
9 Indoor board consumes power from TB3. The power balance should be considered
according to System Design 11-3. "System configuration restrictions".
10 If Transmission booster is needed, be sure to connect the shield wires to the both sides
to the booster.
11 The critical current for choosing power source equipment is approximate
1.4 times of total rated current of the Heat source unit(s) or Indoor unit(s).
12 When System controller (SC) is connected to the system, turn the SW2-1 on.
13 The phases of electricity power must be confirmed to be right used. Phase-reverse, or
phase-missing could break the controllers.
BKC
OCP
NFB
HU
IU
SC
MA R/C
ME R/C
Breaker capacity
Over-current protector
Non-fuse breaker
Heat source unit
Indoor unit
System controller
MA remote controller
ME remote controller
Minimum Wire thickness
G wire
[mm
2
(AWG)]
Power wire
[mm
2
(AWG)]
Model
Symbol
PQRY-P72ZLMU
2.1 (14)
2.1 (14)
PQRY-P96ZLMU
2.1 (14)
2.1 (14)
PQRY-P120ZLMU
2.1 (14)
2.1 (14)
PQRY-P144ZLMU
3.3 (12)
3.3 (12)
PQRY-P168ZLMU
5.3 (10)
5.3 (10)
PQRY-P192ZLMU
5.3 (10)
5.3 (10)
Breaker for current leakage
30 mA or 100 mA 0.1sec. or less
30 mA or 100 mA 0.1sec. or less
30 mA or 100 mA 0.1sec. or less
30 mA or 100 mA 0.1sec. or less
30 mA or 100 mA 0.1sec. or less
30 mA or 100 mA 0.1sec. or less
0000006382.BOOK 96 ページ 2021年7月19日 月曜日 午後4時14分