8. SYSTEM DESIGN GUIDE
WR2-Series-575V
Example-4 Combination of closed type cooling tower and heat exchanger (of other heat source)
In the summer, as the inlet water temperature rises exceeding the set temperature of T1, the bypass port of V1 will
close to lower the inlet water temperature. In the winter, if the inlet water temperature drops below 26°C [79°F], V2 will
conduct water temperature control to keep the inlet water temperature constant.
During the stopping of the heat source water pump, the bypass port of V2 will be closed fully by interlocking.
The start/stop control of the fan and pump of the closed type cooling tower is applied with the step control following
the command of the auxiliary switch XS of V1, thus controlling water temperature and saving motor power.
Heat
source
unit
Closed type
cooling tower
T1 : Proportional type, insertion system thermostat
T2 : Proportional type, insertion system thermostat
V1 : Proportional type, motor-driven 3-way valve
V2 : Proportional type, motor-driven 3-way valve
S : Selector switch
R :
Relay
XS : Auxiliary switch (Duplex switch type)
Relay board
XS
V1
T1
V2
T2
Heat source
water pump
Heat exchanger
Other heat source water