MEES21K047
PQ
R
Y-
P-
Z(
S)
LM
U
-A
1
114
11. M-NET CONTROL
WR2-Series-575V
11-4-3-12. BACnet
®
EW-50A(01)
EW-50A(02)
HUB
For other equipments (Lighting, security, elevator etc.)
000
BACnet
®
000
<Two outdoor units>
<One outdoor unit>
CN41
CN40
EW-50A (AE-200A) can control up to 50 units/groups (including Lossnay).
*To use the BACnet
®
function on EW-50A (AE-200A), BACnet
®
license registration is required.
Indoor unit
MA R/C
MA R/C
(Main)
(Sub)
MA R/C
SRU
Wireless R/C
*1
*1
01
02
03
42
TB15
TB5
TB5
TB2
Transmission Booster
PAC-SF46EPA-G
TB5
TB15
TB15
TB3
TB15
Group 2
Group 1
Group 40
TB3
TB7
TB7
TB7
52
51
OC
OS
TB3
51
OC
CN41
CN40
CN41
CN40
CN41
CN40
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
Indoor unit
ME R/C
ME R/C ME R/C
01
02
03
30
TB5
TB5
TB5
TB2
Transmission Booster
PAC-SF46EPA-G
TB5
ME R/C
101
102
130
180
TB3
Group 2
Group 1
Group 21
TB3
TB3
TB7
TB7
TB7
TB7
TB7
TB3
52
51
OC
OS
TB3
92
91
OC
OS
TB3
96
OC
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
ME R/C ME R/C
Indoor unit
ME R/C
ME R/C
142
144
145
195
41
42
43
44
45
TB5
TB5
TB5
TB5
TB5
Group 32
Group 31
Group 33
Group 34
ME R/C
141
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*2 When a PAR-CT01MAU or PAR-40MAAU is connected to a group, no other MA remote controllers can be connected to the same group.
HUB
CN41
CN40
LAN2
LAN2
BC controller
53
TB02
TB5
TB3
BC controller
(Main)
53
TB02
BC controller
(Main)
93
TB02
Lossnay
Interlocked with
M-NET address 42
0000006382.BOOK 114 ページ 2021年7月19日 月曜日 午後4時14分