2. EXTERNAL DIMENSIONS
WR2-Series-575V
PQRY-P288, 312, 336ZSLMU-A1
Unit: mm(in)
880(34-1
1/16)
20(13/16)
880(34-1
1/16)
550(21-1
1/16)
1450(57-1/8)
1780(70-1/8)
Heat Source unit 2
Heat Source unit 1
T
winning pipe (High pressure)
b
e
a
c
d
T
o BC controller
<Optional parts>
T
o BC controller
<Optional parts>
T
winning pipe (Low pressure)
T
winning pipe connection size
2.T
winning pipe (High pressure) should not be tilted more than 15 degrees from the hori
zontal plane.
3.See the Installation Manual for the details of
T
winning pipe installation.
4.Only use the
T
winning pipe by Mitsubishi (optional parts).
Package unit name
Component unit name
Heat Source unit 1
T
winning pipe Kit(optional parts)
Heat Source unit 2
PQR
Y
-P288ZSLMU-A1
PQR
Y
-P144ZLMU-A1
CMY
-Q200CBK
T
winning pipe~Heat source unit
Unit model
High pressure
Low pressure
c or e
d
P144
P168
ø22.2(7/8)
BC controller~T
winning pipe
High pressure
Low pressure
a
b
ø
28.58(1-1/8)
PQR
Y
-P144ZLMU-A1
PQR
Y
-P312ZSLMU-A1
PQR
Y
-P168ZLMU-A1
PQR
Y
-P144ZLMU-A1
PQR
Y
-P336ZSLMU-A1
PQR
Y
-P168ZLMU-A1
PQR
Y
-P168ZLMU-A1
Note 1.Connect the pipes as shown in the figure above. Refer to the table below for the pip
e size.
ø
34.93(1-3/8)
ø
41.28(1-5/8)
ø28.58(1-1/8)