VIII
Troubleshooting ]
- 29 -
HWE20150
GB
2. DC fan motor (fan motor/indoor control board)
1. CAUTION
A high voltage is applied to the connector for connection to the fan motor (CNMF).
Do not unplug the connector CNMF with the unit energized to avoid damage to the indoor control board and fan motor.
2. Troubleshooting
Symptom: Indoor unit fan does not run.
Indoor controller board fuse (F1)
and fan motor fuse (F2) check
Is the fuse normal?
Is the resistance
between the terminals of
drain pump normal?
Replace the fan motor and the fuse (F2).
Replace the indoor controller board.
Wiring contact check
Contact of fan motor connector (CNMF)
Replace the drain pump.
Is there contact failure?
Wiring recovery
Power supply check (Remove the connector (CNMF))
Measure the voltage in the indoor controller circuit board.
TEST POINT : V
DC
(between 1 (+) and 4 (-) of the fan connector): V
DC
294-325 V DC
TEST POINT : V
CC
(between 5 (+) and 4 (-) of the fan connector): V
CC
15 V DC
Is the voltage normal?
Replace the fan motor.
Replace the indoor
controller board.
Check the operation of fan.
END
Replace the indoor controller board.
Fail
Fail
Check the operation.
Replace the fan motor.
END
OK
OK
Yes
Yes
Yes
Yes
No
No
No
No
1
2