VII
Microprocessor Control ]
- 15 -
HWE20150
GB
2. Drying operation
1. Termoregulating
function
(1) Thermo regulating function (Function to prevent restarting for 3 minutes)
Setting the Dry thermo by the thermo regulating signal and the room temperature (TH21).
Dry thermo ON Room temperature desired tempe 2°F
Dry thermo OFF Room temperature desired temperature
(2) Frozen prevention control
No control function
2. Fan
(1) Indoor fan operation controlled depends on the compressor conditions.
Remote controller setting is not acceptable.
3. Drain
pump
(1) Same control as Cool operation
<How to operate>
1. Press POWER [ON/OFF] button.
2. Press the [F1] button to display Drying.
3. Press the [F2] or [F3] button to set the desired temperature.
The set temperature changes 2°F when the [F2] or [F3] button is
pressed one time. Drying 67 to 87°F
Room temperature
3 min. passed since starting operation
Dry thermo
ON time (min)
Dry thermo
OFF time (min)
Thermo regulating signal
Room temperature (T1)
Over 64°F
ON
T1
83°F
9
3
83°F > T1 79°F
7
3
79°F > T1 75°F
5
3
75°F > T1
3
3
OFF
Unconditional
3
10
Less than 64°F
Dry thermo OFF
Dry thermo
Fan speed notch
ON
[Low]
OFF
Excluding the following
Stop
Room temp. < 64°F
[Low]
Содержание City Multi PEFY-P06NMAU-E4
Страница 1: ......
Страница 5: ...iv HWE20150 GB ...
Страница 7: ...HWE20150 GB ...
Страница 48: ......