VIII
Troubleshooting ]
- 32 -
HWE20150
GB
5. Dipswitch setting (Factory setting)
1. Function
setting
(1) SW1
1) Adress board
(2) SW3
1) Indoor control board
Dipswitch settings must be made while the unit is stopped.
Switch position
Function
Switch setting
ON
OFF
1
Active Thermistor (Intake air
thermistor)
Built-in thermistor on the remote
controller
Indoor unit
2
Filter clogging detection
Available
Unavailable
3
Filter life
2500 hr
100 hr
4
Outdoor air intake
Enabled
Disabled
5
Remote display
Thermo-ON signal
Fan output
6
Humidifier operation
During heating mode
During heating operation
7
Fan speed at heating Thermo-OFF
7
8
Fan speed notch in heating
thermo off
OFF
OFF
Very low
8
ON
OFF
Low
OFF
ON
Preset fan speed
ON
ON
Stop
9
Auto restart after power failure
Enabled
Disabled
10
Power start/stop
Enabled
Disabled
Factory setting
ON
1
2
3
4
5
6
7
8
9
10
Switch position
Function
Switch setting
ON
OFF
1
Unit type
Cooling only
Heat pump
2
Heater available
Heater available
Heater not available
3
-
-
-
4
Heater Control
Heater ON during defrost and
error
Heater OFF during defrost and
error
5
-
-
-
6
-
-
-
7
-
-
-
8
Heating 4-deg up
Disabled
Enabled
9
-
-
-
10
-
-
-
Factory setting
PEFY-P08, 15, 18, 27, 30, 36, 48, 54NMAU-E4
PEFY-P06, 24NMAU-E4
PEFY-P12NMAU-E4
ON
1
2
3
4
5
6
7
8
9
10
ON
1
2
3
4
5
6
7
8
9
10
ON
1
2
3
4
5
6
7
8
9
10
ON
1
2
3
4
5
6
7
8
9
10
The figure at left shows that the switches 1 through 5 are set to ON and 6 through 10 are set to OFF.