VII
Microprocessor Control ]
- 16 -
HWE20150
GB
3. Fan operation
1. Fan
(1) Set by remote controller.
When [Auto] is set, fan speed becomes [Low].
2. Drain
pump
(1) Drain pump control
The drain pump turns ON for the specified amount of time when any of the following conditions is met:
1) ON for 3 minutes after the operation mode is switched from Cool or Drying to another operation mode (Fan).
2) ON for 6 minutes after the float switch is submerged in the water when the float switch control judges the sensor is in the water.
(2) Float switch control
Float switch control judges whether the sensor is in the air or in the water by turning the float switch ON/OFF.
In the water : Detected that the float switch is ON for 15 seconds.
In the air : Detected that the float switch is OFF for 15 seconds.
<How to operate>
1. Press POWER [ON/OFF] button.
2. Press the [F4] button to display Fan.
Type
Fan speed notch
3 Auto type
[Low], [Mid], [High], [Auto]
ON
OFF
15sec.
15sec.
15sec.
1min.30sec.
1min.30sec.
Float SW
In the water
In the air
In the water
Error
postponement
Drain pump
abnormal