• All AHU additional refrigerant calculations must be completed by BDT. The calculation is based
on the AHU coil volume (BDT has this data).
• Additional refrigerant can be charged into the system while under a vacuum. In some situations
the system will equalise to the bottle pressure before all of the additional refrigerant is in the
system. The remaining refrigerant can be charged in to the low side of the system while it is
running on either heating or cooling during the initial commissioning process.
• Any additional refrigerant must be liquid charged into the system.
• Additional refrigerant levels should be noted on each outdoor unit.
DIP SWITCHES OUTDOOR UNITS (S SERIES)
104
The
black
square
(
■
) indicates
a
switch
position.
PUM
Y-P
112/125/140YKM-A(-BS)
Continue to the next page
8-5.
INTERNA
L SWITCH
FUNCTION
TABLE
PUM
Y-P
112/125/140VKM-A(-BS)
Switch
Step
Function
Operation in Each Switch Setting
Remarks
Purpose
Additional Information
ON
OFF
When to Set
SWU1 1st digit
SWU2 2nd
digit
Rotary switch
Before turning
the power ON
<Initial settings>
SW1
Digital
Display
Switch
1~8
Can be set either during
operation or not.
<Initial settings>
SW2
Function
Switch
1 Selects operating system startup
With centralized
controller
Without centralized
controller
Before turning
the power ON
<Initial settings>
Turn ON when the centralized controller is
connected to the outdoor unit.
—
2 Connection information clear switch
Clear
Do not clear
When relocating units or connecting additional
units.
—
3 Abnormal data clear switch input
Clear
abnormal data
Normal
OFF to ON any time after
the power is turned on.
To delete a check code history.
4 Pump down
Run
adjustment
mode
Normal
During compressor
running
To facilitate outdoor unit the pumping down
operation.
Frequency = Fixed to 65 Hz
Indoor-electronic expansion valve = Fully open
Outdoor fan step = Fixed to 10
Please refer to a section referring
to the pumping down on outdoor
unit’s Installation Manuals.
It might not be possible to collect
all the refrigerant if the amount is
excessive.
5
—
—
—
—
—
—
6
—
—
—
—
—
—
SW3 Trial
operation
1 ON/OFF from outdoor unit *
ON
OFF
Any time after the
power is turned ON.
<Initial settings>
—
—
2 Mode setting
Heating
Cooling
—
—
SW4/
SW8
Model
Switch
1~6
MODEL SELECTION 1:ON 0:OFF
Before the power
is turned ON.
<Initial settings>
Set for each capacity.
—
—
SW5
Function
Switch
1
Demand control setting for Demand
Responce Mode (DRM)
DRM
Existing
demand mode**
Can be set when
off or during
operation
<Initial settings>
Turn ON to activate the demand control for DRM. Do not turn this ON if the unit is in
outside Australia
2 Change the indoor unit's LEV
opening at start-up
Enable
Normal
To set the LEV opening at start-up higher than usua
l.
(Qj <14 + 500 pulses, 14
[
Qj + 75 pulses)
To improve the operation with the LEV almost
clogged.
up become louder.
3
—
—
—
—
—
4 Auxiliary heater
—
—
OFF to ON during
compressor running.
Turn ON when an auxiliary heater is connected.
(It transmits a connection permission signal of
the auxiliary heater to the connected indoor unit.)
Turn ON only when the auxiliary
heater is connected and
operated.
5 Change the indoor unit's LEV
opening at defrost
Enable
Normal
Can be set when
OFF or during
operation
To set the LEV opening higher than usual
during defrosting operation.
(Only Qj
[
10 is valid, + 300 pulses)
To avoid the discharge temperature increase
the defrosting operation become
louder.
6 Switching the target sub cool
(Heating mode)
Enable
Normal
To decrease the target sub cool value.
To reduce the discharge temperature
decrease due to refrigerant liquid
accumulation in the units.
generated if the sub cool value is
too small.
* Test run on PWFY series cannot be run by the outdoor unit. Use a switch on the indoor unit or a remote controller to perform test run.
** Refer to "8-6. OUTDOOR UNIT INPUT/OUTPUT CONNECTOR".
SWU2
(2nd digit)
0 12
3
45
67
89
SWU1
(1st digit)
0 12
3
45
67
89
1
ON
OFF
2 3 4 5 6 7 8
SW4
MODELS
PUMY-P112VKM
SW8
PUMY-P125VKM
PUMY-P140VKM
1
ON
OFF
2 3 4 5 6
1
ON
OFF
2 3 4 5 6
1
ON
OFF
2 3 4 5 6
1
ON
OFF
2
1
ON
OFF
2
1
ON
OFF
2
SW4
MODELS
PUMY-P112YKM
SW8
PUMY-P125YKM
PUMY-P140YKM
1
ON
OFF
2 3 4 5 6
1
ON
OFF
2 3 4 5 6
ON
OFF
1
ON
OFF
2
1
ON
OFF
2
1
ON
OFF
2
1 2 3 4 5 6
SWU2
(2nd digit)
0 12
3
45
67
89
SWU1
(1st digit)
0 12
3
45
67
89
1
ON
OFF
2 3 4 5 6 7 8
1
ON
OFF
2 3 4 5 6
1
ON
OFF
2
1
ON
OFF
2 3 4 5 6 7 8
OCH549
ADDITIONAL REFRIGERANT CALCULATIONS
PUMY-P-V(Y)KM-A(-BS)
Содержание BDT CITY MULTI
Страница 41: ...41 S SERIES OUTDOOR UNIT WIRING INPUTS AND OUTPUTS CITY MULTI ONLY ...
Страница 42: ...42 INDOOR UNIT WIRING INPUTS AND OUTPUTS CITY MULTI ONLY INPUTS AND OUTPUTS Continued ...
Страница 44: ...44 RECOMMENDED M NET WIRING PROCEDURE CABLE LIMITATIONS AND SYSTEM EXAMPLES ...
Страница 47: ...47 ...
Страница 48: ...48 BASIC SYSTEM M NET WIRING AND ADDRESSING EXAMPLE M NET ADDRESSING Continued ...
Страница 63: ...63 DIP SWITCHES INDOOR UNITS ...
Страница 68: ...68 Stanley Street Building Auckland ...