55
3. Piping Design
AN1 2nd
4 - 106
S.D. R2
MEE14K009
Amount of factory charged refrigerant
The above calculation result of the amount of refrigerant to be charged must become below the value in the table below.
*1 Amount of additional refrigerant to be charged on site
Outdoor unit
Model
P250
P300
P400
P450
P350
P200
Charged amount
10.3 kg
11.8 kg
9.5 kg
Limitation of the amount of refrigerant to be charged
Sample calculation
Indoor
Outdoor
A: ø28.58 40m
1: 50
a: ø6.35
B: ø9.52
10m
2: 250
b: ø9.52
C:
3: 15
c: ø6.35
ø12.70 20m
4: 20
d: ø6.35
D:
5: 140
e: ø9.52
ø9.52
5m
6: 200
P700
The total length of each liquid line is as follows:
ø28.58: A = 40 m
ø19.05: F + G = 4 m
ø12.70: C = 20 m
ø9.52: B + D + E + b + e + f = 35 m
ø6.35: a + c + d = 25 m
Therefore,
<Calculation example>
Additional refrigerant charge
= 40 × 0.33 + 4 × 0.14 + 20 × 0.11 + 35 × 0.054 + 25 × 0.021 + 6
+ 2 + 2 + 6
= 34.4 (34.375) kg
f: ø9.52
E: ø9.52
5m
F: ø19.05
3m
10m
5m
5m
10m
5m
5m
G: ø19.05
1m
• When the piping length from the outdoor unit to the farthest indoor unit is longer than 30.5 m (100 ft)
Amount of
additional
charge (kg)
=
High-pressure pipe
ø28.58 total length
× 0.33 (kg/m)
+
High-pressure pipe
ø22.2 total length
× 0.21 (kg/m)
+
High-pressure pipe
ø19.05 total length
× 0.14 (kg/m)
+
High-pressure pipe
ø15.88 total length
× 0.1 (kg/m)
+
Liquid pipe ø15.88
total length
× 0.18 (kg/m)
+
Liquid pipe ø12.7
total length
× 0.11 (kg/m)
+
Liquid pipe ø9.52
total length
× 0.054 (kg/m)
+
Liquid pipe ø6.35
total length
× 0.021 (kg/m)
+
Total capacity of
outdoor units
Amount
(to be added for standard or
main BC controller)
+
Main BC controller
Amount
P200
3.0kg
HA-type
2.0kg
P250
4.5kg
P300
4.5kg
P350–900
6.0kg
+
Number of sub BC
controllers
Amount
(to be added for sub
BC controller)
+
Total capacity of connected
indoor units
Amount
(to be added for
indoor unit)
1
1.0kg
80 or below
2.0kg
2
2.0kg
81 to 160
2.5kg
161 to 330
3.0kg
331 to 390
3.5kg
391 to 480
4.5kg
481 to 630
5.0kg
631 to 710
6.0kg
711 to 800
8.0kg
801 to 890
9.0kg
891 to 1070
10.0kg
1071 to 1250
12.0kg
1251 or above
14.0kg
+
Outdoor unit model
Amount
(to be added for
outdoor unit)
Single
P200 to P250YLM
0kg
P300 to P350YLM
0kg
Combination
P400 to P550YSLM
0kg
P600 to P800YSLM
0kg
P850YSLM
5.5kg
P900YSLM
11.0kg
Maximum amount of
refrigerant *1
Outdoor unit model
27.5kg
33.5kg
37.0kg
39.0kg
52.0kg
59.0kg
62.5kg
75.0kg
79.5kg
84.0kg
89.0kg
P200
YLM
P250
YLM
P300
YLM
P350
YLM
P500
YSLM
P550
YSLM
52.0kg
52.0kg
P400
YSLM
P450
YSLM
P600
YSLM
P650
YSLM
P700
YSLM
P850
YSLM
P900
YSLM
79.5kg
79.5kg
P750
YSLM
P800
YSLM
0000003417.BOOK 106 ページ 2014年10月22日 水曜日 午前10時35分
ADDITIONAL REFRIGERANT CALCULATIONS (R2 SERIES) example
Содержание BDT CITY MULTI
Страница 41: ...41 S SERIES OUTDOOR UNIT WIRING INPUTS AND OUTPUTS CITY MULTI ONLY ...
Страница 42: ...42 INDOOR UNIT WIRING INPUTS AND OUTPUTS CITY MULTI ONLY INPUTS AND OUTPUTS Continued ...
Страница 44: ...44 RECOMMENDED M NET WIRING PROCEDURE CABLE LIMITATIONS AND SYSTEM EXAMPLES ...
Страница 47: ...47 ...
Страница 48: ...48 BASIC SYSTEM M NET WIRING AND ADDRESSING EXAMPLE M NET ADDRESSING Continued ...
Страница 63: ...63 DIP SWITCHES INDOOR UNITS ...
Страница 68: ...68 Stanley Street Building Auckland ...