background image

57

105

The
 black

 square

 (

) indicates

 a

 switch

 position.

1

ON

OFF

2 3 4 5 6 7 8

1

ON

OFF

2 3 4 5 6

1

ON

OFF

2

<Initial settings>

Switch Step

Function

Operation in Each Switch Setting

Remarks

Purpose

Additional Information

ON

OFF

When to Set

SW5

function

switch

7

When the outdoor unit is in HEAT 

operation, slightly opens the electronic 

expansion valve on the indoor unit which 

is in FAN, STOP, COOL or thermo-OFF**.

Active 

Inactive

Can be set when 

OFF or during 

operation

To open the LEV opening higher for units other than in 

HEAT operation. To avoid a refrigerant shortage (less 

capacity) due to refrigerant liquid accumulation in the 

units which are not in operation.

 A refrigerant 

 noise might be generated 

in units other than the one in operation.

8

When the outdoor unit is in operation, 

fully opens the electronic expansion 

valve on the indoor unit which is in 

FAN, COOL, STOP, or thermo-OFF.***

Enable

Normal

Before turning the 

power ON.

 To reduce the room temperature increase by setting 

the LEV opening lower for the units in thermo-OFF 

operation.

The refrigerant is more likely to collect in the units with 

thermo-OFF operation, and cause the units refrigerant 

shortage. (Results in less capacity and increase of 

discharge temperature.)

SW6

function

switch

1

<Initial settings>

2

Switch of current limitation 

reading 

in a different way

Enable

Normal

Before turning 

the power ON.

To lower the primary current limit by 3A.

This switch is used for a single phase model with a 

The performance of the unit might be somewhat 

limited on this mode.

3

4 Change of defrosting control

Enable

(For high 

humidity)

Normal

Can be set 

when OFF 

or during 

operation

To shorten the defrosting prohibition time in high 

humidity (or heavy snow) regions, in order to reduce 

malfunctions caused by frost .

The performance of the HEAT operation is somewhat 

reduced since the defrosting operation is frequently 

performed.

5 Ignore refrigerant 

abnormality

Enable

Normal

To ignore the error detection of excessive charge of 

refrigerant. The unit can be excessively charged with 

refrigerant depending on the operating condition.

Make sure that the unit is not excessively charged 

with refrigerant before starting operation when 

servicing or installing the units.

6 Switching the target discharge

pressure (Pdm)

Enable

Normal

To raise the performance by setting the PDm higher 

during HEAT operation.

Power consumption is raised due to a higher 

frequency. (The performance would not be raised at the 

maximum operating frequency.)

7

Switching (1) the target evaporation

temperature (ETm)

Enable

Normal

To raise/reduce the performance by changing the 

target ETm during COOL operation.

Switch to raise the performance: raises the performance

Switch to reduce the performance: prevents dew condensation

Switching it to raise the performance, it raises the power 

consumption, and produces more dew condensation.

Switching it to reduce the performance, it makes the 

8

Switching (2) the target evaporation

temperature (ETm)

Enable

Normal

SW7

function

switch

1 Ignore current sensor

abnormality

Enable

Normal

After turning 

the power ON. <Initial settings>

To perform a test run for electrical parts alone without 

running the compressor. 

Make sure to connect the connectors to the compressor 

after checking the electrical parts.Be careful not to get 

an electric shock while working on electrical parts.

2 Setting to energise the freeze 

stat heater (optional part)

During 

heating 

operation 

only****

Include when 

the heating 

operation is 

OFF.*****

Can be set when 

OFF or during 

operation

while the HEAT operation is stopped. 

Power consumption raises while the operation is 

stopped.

3

4 Maximum frequency down at 1 

hour after COOL operation

Enable

Normal

Can be set when 

OFF or during 

operation

To reduce dew condensation on the indoor unit by 

lowering the frequency.

5

6 Forced defrost

Forced 

defrost

Normal

During compressor

running in HEAT 

mode.

Turn ON when it is necessary to perform the defrosting 

operation forcedly. 

(

Effective only at start-up, or 10 

minutes after the last defrosting operation)

It performs the defrosting operation forcedly.

(HEAT operation is stopped temporarily.)

SW9

Function

Switch

1 Auto change over from remote 

controller 

(IC with the minimum address) Enable*

Disable

Before turning the 

power ON

<Initial settings>

Enables the indoor unit with the minimum address 

to select AUTO mode, and switches the operation 

mode of the other indoor units to the same mode.

Cannot be set when the centralized control 

is ON.

2 Switching the Silent/ Demand 

mode

Demand 

control

Silent 

mode

Can be set when 

OFF or during 

operation

About the Silent mode/Demand control setting, refer to 

"8-6. OUTDOOR UNIT INPUT/OUTPUT CONNECTOR".

 

 

When a PWFY series is connected, this function is always disable regardless of the switch.

  

SW5-7 Opens the indoor-

electronic expansion valve as a countermeasure against the indoor unit in FAN, COOL, STOP, or thermo-OFF operation with refrigerant-shortage status due to an accumulation of liquid refrigerant 

 

in the indoor unit.

  

SW5-8 Countermeasure against room temperature rise for indoor unit in FAN, COOL, and thermo-OFF (heating) mode.

 

During heating operation and the ambient temperature is 4

:

(39°F) or below, the freeze prevention heater is energized.

 

During heating mode is OFF (include thermo-OFF in cooling mode), and the ambient temperature is 4

:

(39°F) or below, the freeze prevention heater is energized.

1

ON

OFF

2 3 4 5 6

SW6-6

OFF ON

Target Pdm (kg/cm²) 29.5 31.5

SW6-7

OFF ON OFF ON

SW6-8

OFF OFF ON

ON

Target ETm (

:

)

9

11

6

14

*

**

***

****

*****

OCH549

to reduce ice build up. Set the base heater to ON 

Energises electric heater element within drain tray

PUMY-P-V(Y)KM-A(-BS)

Содержание BDT CITY MULTI

Страница 1: ...rtance of well trained highly skilled technical support staff Both companies share the belief that quality support strengthens the product by providing valuable design installation service and maintenance information quickly and efficiently BDT engineers and support staff undergo regular factory training to confidently ensure that we are supplying the most up to date and quality advice Confidentia...

Страница 2: ...nd specifications change so differences may exist between the content of this manual and final product specifications Always check the BDT website or contact Technical Services on 0800 163 526 to confirm current product data before carrying out any prescribed work The contents and instructions within this booklet do not in any way negate local bylaws or New Zealand standards and regulations nor do...

Страница 3: ...nd Outputs M Net Wiring Procedure M Net Addressing Piping and Wiring Schematics Additional Refrigerant Calculations Dip Switches Auto Changeover Indoor Unit Installation Setting Template SECTION B Installation and Commissioning Focus Back page in sleeve Pre commissioning Site Inspection Form Pre commissioning Check Sheet Indoor Unit Installation Setting Project Piping and Wiring Schematics 04 07 1...

Страница 4: ...0A installations is to comply with AS NZ Standard 1677 Part 2 Copper tube of the correct wall thickness must be used SEALED PIPE Hard and soft drawn copper tube stored on site prior to installation must have plastic end caps fitted to prevent ingress of moisture and foreign objects Bends and fittings should be kept dry and in the original packing prior to installation PENETRATIONS All building pen...

Страница 5: ...an occur Risers can be capped prior to the BC boxes and pressurised from the outdoor unit service valve connections Pressure for overnight testing to 100 psi using dry nitrogen A final system pressure test of 500 psi using dry nitrogen held for 24 hours is required to prove complete system tightness prior to evacuation The results must be noted 05 EFFECTIVE EVACUATION TECHNIQUES Effective evacuati...

Страница 6: ...cal to the system s long term operation and warranty compliance When possible it is preferable to use copper lines for evacuation purposes as gauge hoses are porous when trying to measure accurate deep vacuum VACUUM MEASUREMENT COMPARISONS 1 TORR 1mm HG 1 TORR 1000 1000 microns microns 1000 29 88 HG inches or mercury microns 1mm HG 1 Connect the vacuum pump check valve vacuum gauge charge line wit...

Страница 7: ... in max To BC controller Twinning pipe low pressure side Twinning pipe high pressure side On site piping low pressure connecting pipe between outdoor units On site piping low pressure main pipe to BC controller On site piping high pressure main pipe to BC controller Straight run of pipe that is 500 mm 19 11 16 in or more See the Installation Manual for the details of Twinning pipe installation See...

Страница 8: ... around the edges of through holes for pipes and wires on the unit allow water or mice to enter the unit and damage its parts Close these gaps with filler plates This unit allows two types of pipe routing Bottom piping Front piping To prevent small animals water and snow from entering the unit and damaging its parts close the gap around the edges of through holes for pipes and wires with filler pl...

Страница 9: ...ed H H 3 The vertical separation between units H must be 0 1 m 3 15 16 in or below In the figure on the right because the distance is more than 0 1 m 3 15 16 in the oil accumulates in Unit 1 when Unit 2 is in operation and Unit 1 is stopped H H 4 The vertical separation between units H must be 0 1 m 3 15 16 in or below In the figure on the right because the distance is more than 0 1 m 3 15 16 in t...

Страница 10: ...may cause improper operation CAUTION Field piping Twinning kit Twinning kit Field piping Field piping Field piping Twinning kit The length of the straight pipe must be 500 mm 19 11 16 in or longer The length of the straight pipe must be 500 mm 19 11 16 in or longer The length of the straight pipe must be 500 mm 19 11 16 in or longer See the following drawing for connecting the pipes between the ou...

Страница 11: ...mm 7 7 8 in or less 200mm 7 7 8 in or less Outdoor unit1 Outdoor unit 2 Outdoor unit 1 Outdoor unit 2 Outdoor unit 3 Twinning pipe 1 Twinning pipe 2 To Indoor unit PUHY P400YSKB A PUHY EP500YSLM A PUHY P950YSKB A PUHY EP800YSLM A 0000003416 BOOK 55 ページ 2014年11月11日 火曜日 午前9時34分 ...

Страница 12: ...e edges of through holes for pipes and wires on the unit allow water or mice to enter the unit and damage its parts Close these gaps with filler plates This unit allows two types of pipe routing Bottom piping Front piping To prevent small animals water and snow from entering the unit and damaging its parts close the gap around the edges of through holes for pipes and wires with filler plates CAUTI...

Страница 13: ...s is installed inexperienced technicians that use the glass may overcharge the refrigerant A Install the piping so that oil will not accumulate in the stopped outdoor unit 1 unit 1 unit 2 unit 3 unit 1 unit 2 unit 3 unit 1 unit 2 unit 3 The NG example shows that oil accumulates because the units are installed on a reverse gradient while unit 1 is in operation and unit 3 is stopped 2 unit 1 unit 2 ...

Страница 14: ...ler in case of connected Indoor unit sized P100 P140 with 2 ports Note6 It is also possible to connect Indoor unit sized P100 P140 with 1 port set DIP SW 4 6 to OFF Note7 Individual indoor units grouped together to connect to the BC controller via one port cannot operate individually in heating and cooling modes at the same time I e they must all function in either heating However the cooling capa...

Страница 15: ...ends Note5 Set DIP SW 4 6 to ON of BC controller in case of connected Indoor unit sized P100 P140 with 2 ports Note6 It is also possible to connect Indoor unit sized P100 P140 with 1 port set DIP SW 4 6 to OFF Note7 Individual indoor units grouped together to connect to the BC controller via one port cannot operate individually in heating and cooling modes at the same time I e they must all functi...

Страница 16: ...ur local distributor 0 10 20 30 40 50 60 70 0 5 10 15 Height difference between the main BC controller and indoor unit m Note1 No Header usable on PURY system Note2 Indoor unit sized P100 P250 should be connected to BC controller via Y shape joint CMY R160 J1 Note3 Indoor unit sized P100 P250 does NOT share BC controller ports with other Indoor units Note4 As bends cause pressure loss on transport...

Страница 17: ...utdoor unit and BC controller m Tot al extended pipe length m 200 300 400 500 600 700 800 900 1000 10 20 30 40 50 60 70 80 90 100 110 Distance between outdoor unit and BC controller m Tot al extended pipe length m PURY P400 450 500 550YSLM A 200 300 400 500 600 700 800 900 1000 10 20 30 40 50 60 70 80 90 100 110 Distance between outdoor unit and BC controller m Tot al extended pipe length m PURY P...

Страница 18: ... c 165 541 190 623 Farthest IU from first Joint L2 C D E g B c 40 131 40 131 Height between OU and IU OU above IU 0 5 H 164 Height between OU and IU OU under IU H 40 131 Height between IU and IU h1 15 49 OU Outdoor Unit IU Indoor Unit Piping A size selection rule mm in Outdoor unit d i u q i L e p i P Pipe Gas PUHY P200YKB ø9 52 3 8 ø22 20 7 8 PUHY P250YKB ø9 52 3 8 1 ø22 20 7 8 PUHY P300YKB ø9 52...

Страница 19: ...100VBK3 at the Outdoor unit s external drawing Piping B C D E size selection rule mm in Total down stream Indoor capacity Pipe Liquid Pipe Gas 8 5 8 8 5 1 ø 8 3 2 5 9 ø 0 4 1 P 4 3 5 0 9 1 ø 8 3 2 5 9 ø 0 0 2 P 1 4 1 P 8 7 0 2 2 2 ø 8 3 2 5 9 ø 0 0 3 P 1 0 2 P 8 1 1 8 5 8 2 ø 2 1 0 7 2 1 ø 0 0 4 P 1 0 3 P 8 1 1 8 5 8 2 ø 8 5 8 8 5 1 ø 0 5 6 P 1 0 4 P 8 3 1 3 9 4 3 ø 4 3 5 0 9 1 ø 0 0 8 P 1 5 6 P 8...

Страница 20: ...U and IU OU under IU H 40 131 Height between IU and IU h1 15 49 OU Outdoor Unit IU Indoor Unit For Piping size M N S T please refer to specification of the Twinning kit CMY Y300VBK3 at the Outdoor unit s external drawing Piping B C D E size selection rule mm in Total down stream Indoor capacity Pipe Liquid Pipe Gas 8 5 8 8 5 1 ø 8 3 2 5 9 ø 0 4 1 P 4 3 5 0 9 1 ø 8 3 2 5 9 ø 0 0 2 P 1 4 1 P 8 7 0 2...

Страница 21: ...er to carry out service enter the size and length of each liquid pipe and additional refrigerant charge amounts in the spaces provided on the Refrigerant amount plate on the outdoor unit Calculation of additional refrigerant charge Calculate the additional charge using the liquid pipe size and length of the extended piping and total capacity of connected indoor units Calculate the additional refri...

Страница 22: ...ant charge Refrigerant for the extended piping is not included in the outdoor unit when the unit is shipped from the factory Therefore charge each refrigerant piping system with additional refrigerant at the installation site In addition in order to carry out service enter the size and length of each liquid pipe and additional refrigerant charge amounts in the spaces provided on the Refrigerant am...

Страница 23: ...ipe and additional refrigerant charge amounts in the spaces provided on the Refrigerant amount plate on the outdoor unit Calculation of additional refrigerant charge Calculate the additional charge using the liquid pipe size and length of the extended piping and total capacity of connected indoor units Calculate the additional refrigerant charge using the procedure shown to the right and charge wi...

Страница 24: ...both sides of the unit Condition 100 3 15 16 300 11 13 16 50 1 31 32 15 19 32 L W Minimum space behind the unit Minimum space on both sides of the unit Condition 100 3 15 16 h 300 11 13 16 h 50 1 31 32 h 15 19 32 h L W Should be shorter than the unit height Should be shorter than the unit height h 500 19 11 16 500 19 11 16 500 19 11 16 450 17 23 32 h h 2 3 3 2 7 1 0 5 4 h 2 3 3 2 7 1 0 5 4 L W W h...

Страница 25: ...e passage space for each six units three units EP400 450 The space on both sides of a given group of units is minimum There are walls in the front and the back of a given group of units There is a wall on one side There is a wall on one side and either the front or the back of a given group of unit The space on both sides of a given group of units is minimum h 500 19 11 16 300 11 13 16 h 450 17 23...

Страница 26: ...ps 2 groups Fig 4 2 13 Stacked groups arrangement 4 2 1 Spacing individual PUMY P YKM VKM Follow Fig 4 2 2 7 to space individual PUMY P YKM VKM at the installation site 4 2 2 Spacing grouped PUMY P YKM VKM Follow Fig 4 2 8 13 to space grouped PUMY P YKM VKM at the installation site Leave 10 mm 13 32 space or more between PUMY P YKM VKM units PUMY P YKM VKM can connect Indoor unit sized P15 to P140...

Страница 27: ...nchor bolt mounting positions However local council regulations relating to seismic mounting may call for additional requirements Please always confirm and comply with your local regulations and standards NOTE If anti vibration mounts are required it must be in the form of absorption isolation pads Under no circumstances should spring type mounts be used ...

Страница 28: ... unprotected from the wind situate the air outlet of the unit so that it is not directly exposed to strong winds Strong wind entering the air outlet may impede the normal airflow and a malfunction may result The following shows two examples of precautions against strong winds Install an optional air guide if the unit is installed in a location where strong winds may directly enter the air outlet F...

Страница 29: ...such a way that the top end of the anchor bolt do not stick out more than 30 mm 1 3 16 in This unit is not designed to be anchored with post installation type anchor bolts although by adding fixing brackets anchoring with such type of anchor bolts becomes possible Individual installation P200 400 EP200 350 Collective installation Take into consideration the durability of the base water drainage ro...

Страница 30: ...width of the unit leg D anchor bolt 3 locations to fix with screws A B C Secure the unit with anchor bolts as shown in the figure below so that the unit will not topple over in strong winds or during an earthquake Install the unit on a durable base made of materials such as concrete or angle steel Take appropriate anti vibration measures e g vibration damper pad vibration isolation base to keep vi...

Страница 31: ... and a 30VDC M Net control Indoor units with a capacity code of P200 or larger will require a 380 415VAC supply In addition to this wall controllers and external inputs outputs can also be wired to the indoor unit if required OUTDOOR UNITS Each outdoor unit will require 380 415VAC supply and 2x M Net control connections M Net 1 TB3 indoor outdoor transmission cable 24 30VDC M Net 2 TB7 central con...

Страница 32: ...Y P100VBM E 1 25 0 120 1 00 PLFY P125VBM E 1 34 0 120 1 07 PLFY P VLMD E Power supply IFM Volts Hz Range 10 MCA A 50 60Hz Output kW FLA A 50 60Hz PLFY P20VLMD E 220 240V 50Hz 220 230V 60Hz Max 264V Min 198V 0 45 0 46 0 015 0 36 0 37 PLFY P25VLMD E 0 45 0 46 0 015 0 36 0 37 PLFY P32VLMD E 0 45 0 46 0 015 0 36 0 37 PLFY P40VLMD E 0 50 0 53 0 015 0 40 0 42 PLFY P50VLMD E 0 51 0 54 0 020 0 41 0 43 PLF...

Страница 33: ... 0 26 2 48 3 18 PEFY P200VMH E 380 415V 50Hz 380 415V 60Hz Max 456V Min 342V 2 03 2 33 0 76 1 62 1 86 PEFY P250VMH E 2 50 2 88 1 08 2 00 2 30 PEFY P200VMHS E 220 240V 50Hz 220 240V 60Hz Max 264V Min 198V 7 00 0 87 5 60 PEFY P250VMHS E 7 50 0 87 6 00 PEFY P VMA E Power supply IFM Volts Hz Range 10 MCA A Output kW FLA A PEFY P20VMA E 220 240V 50Hz 220 240V 60Hz Max 264V Min 198V 1 03 0 085 0 82 PEFY...

Страница 34: ... E Power supply IFM Volts Hz Range 10 MCA A Output kW FLA A PKFY P63VKM E 220 240V 50Hz 220V 60Hz Max 264V Min 198V 0 36 0 056 0 29 PKFY P100VKM E 0 63 0 056 0 50 PCFY P VKM E Power supply IFM Volts Hz Range 10 MCA A Output kW FLA A PCFY P40VKM E 220 240V 50Hz 220V 60Hz Max 264V Min 198V 0 35 0 090 0 28 PCFY P63VKM E 0 41 0 095 0 33 PCFY P100VKM E 0 81 0 160 0 65 PCFY P125VKM E 0 95 0 160 0 76 PFF...

Страница 35: ... 400 415 Max 456V Min 342V 13 2 9 7 0 06 x 2 4 46 4 24 4 09 PUMY P125YKM 13 3 5 7 0 06 x 2 5 53 5 26 5 07 PUMY P140YKM 13 3 9 7 0 06 x 2 7 23 6 87 6 62 PUMY P VKM Units Power supply Compressor FAN RLA A Hz Volts Voltage range MCA A Output kW SC A Output kW PUMY P112VKM 50 220 230 240 Max 264V Min 198V 29 5 2 9 14 0 06 x 2 14 03 13 42 12 86 PUMY P125VKM 29 5 3 5 14 0 06 x 2 17 26 16 51 15 82 PUMY P...

Страница 36: ... P450YKB A BS 39 7 12 4 8 0 92 0 92 PUHY P850YSKB A BS PUHY P400YKB A BS 35 2 10 8 8 0 92 55 8 53 0 51 1 57 8 54 9 52 9 PUHY P450YKB A BS 39 7 12 4 8 0 92 0 92 PUHY P900YSKB A BS PUHY P450YKB A BS 39 7 12 4 8 0 92 0 92 59 1 56 2 54 1 61 1 58 0 55 9 PUHY P450YKB A BS 39 7 12 4 8 0 92 0 92 PUHY P950YSKB A BS PUHY P250YKB A BS 18 2 6 9 8 0 92 57 1 54 2 52 3 58 4 55 5 53 5 PUHY P300YKB A BS 22 9 8 1 8...

Страница 37: ...92 PUHY EP300YLM A BS 8 1 8 0 92 PUHY EP850YSLM A BS PUHY EP250YLM A BS 61 3 6 9 8 0 92 43 0 40 9 39 4 46 8 44 5 42 9 PUHY EP300YLM A BS 8 1 8 0 92 PUHY EP300YLM A BS 8 1 8 0 92 PUHY EP900YSLM A BS PUHY EP300YLM A BS 64 8 8 1 8 0 92 45 9 43 6 42 0 49 0 46 5 44 8 PUHY EP300YLM A BS 8 1 8 0 92 PUHY EP300YLM A BS 8 1 8 0 92 PUHY EP950YSLM A BS PUHY EP300YLM A BS 71 9 8 1 8 0 92 51 2 48 6 46 8 54 0 51...

Страница 38: ... 9 48 1 48 1 45 7 44 1 PURY P400YLM A BS 10 9 8 0 92 PURY P900YSLM A BS PURY P450YLM A BS 76 8 12 4 8 0 92 53 2 50 6 48 7 54 8 52 0 50 1 PURY P450YLM A BS 12 4 8 0 92 PURY EP YLM Unit Combination Units Power supply Compressor FAN RLA A 50 60Hz Hz Volts Voltage range MCA A Output kW SC A Output kW Cooling Heating PURY EP200YLM A BS 50 60 380 400 415 Max 456V Min 342V 16 1 5 6 8 0 92 9 2 8 7 8 4 10 ...

Страница 39: ... 220 0 85 0 58 230 0 63 240 0 68 CMB P1010V G1 220 1 04 0 71 230 0 77 240 0 83 CMB P1013V G1 220 1 34 0 92 230 1 00 240 1 07 CMB P1016V G1 220 1 63 1 12 230 1 22 240 1 30 CMB P108V GA1 220 0 85 0 58 230 0 63 240 0 68 CMB P1010V GA1 220 1 04 0 71 230 0 77 240 0 83 CMB P1013V GA1 220 1 34 0 92 230 1 00 240 1 07 CMB P1016V GA1 220 1 63 1 12 230 1 22 240 1 30 CMB P1016V HA1 220 1 63 1 12 230 1 22 240 ...

Страница 40: ...1A Minimum applicable load 1mA at DC 2 Low noise mode CN3D DipSW4 4 OFF X CN3D Preparations in the field Maximum cable length is 10m Adapter 2 Outdoor unit control board 2 3 1 X Relay The sound pressure level is reduced by controlling the maximum fan frequency and compressor frequency Note The sound pressure level can not be reduced when neither the fan frequency nor the compressor frequency are m...

Страница 41: ...41 S SERIES OUTDOOR UNIT WIRING INPUTS AND OUTPUTS CITY MULTI ONLY ...

Страница 42: ...42 INDOOR UNIT WIRING INPUTS AND OUTPUTS CITY MULTI ONLY INPUTS AND OUTPUTS Continued ...

Страница 43: ...system Star point connections are not acceptable except when wiring in a sub BC and must have only one star point connection leading to the sub BC as shown on the piping and wiring schematic 2 The second M Net starts from TB7 on the first outdoor unit it is 22 28VDC and daisy chains from system central controllers and all other outdoor units on all systems that are connected to the central control...

Страница 44: ...44 RECOMMENDED M NET WIRING PROCEDURE CABLE LIMITATIONS AND SYSTEM EXAMPLES ...

Страница 45: ...e conduit 3 Earth and neutral connection and testing back to MCC must be carried out by an electrician prior to powering up the outdoor unit 4 Do not connect 230 volts to M Net connection This will result in catastrophic board failure 5 Two core screened 1 25mm2 cables must be used for all M Net wiring Failure to do so will void all warranty and cause control system errors Royal Thai Embassy Welli...

Страница 46: ...and label each item of plant with permanent marker or other labelling system with the following Address Indoor Outdoor BC Name Port Number R2 equipment only ADDRESSING MUST FOLLOW THE PIPING AND WIRING SCHEMATICS Rotary Switch Operation Addresses are set using numerical rotary switches There are two rotary tumblers for address setting the 10 s and the 1 s For R2 indoor units a port setting is requ...

Страница 47: ...47 ...

Страница 48: ...48 BASIC SYSTEM M NET WIRING AND ADDRESSING EXAMPLE M NET ADDRESSING Continued ...

Страница 49: ...t addresses An A3 piping and wiring schematic for this project is located in the sleeve at the back of this booklet If the installation varies from this schematic in any way it should be identified on the schematic and returned to BDT to re write into an as built schematic of the system on completion of installation A copy of the as built piping and wiring schematics should be left on site as a re...

Страница 50: ...50 Job Name Quote Number M Net Wiring blue lines Pipe Sizes Unit Address Number Piping red dotted lines Model Numbers Group Names Supply Wiring Black lines EXAMPLE SCHEMATIC ...

Страница 51: ...300 m A B C d 150 m B C d 30 m 50 meters or less If the outdoor unit is lower 40 meters or less 15 meters or less Use an optional branch piping kit CMY Y62 G E Total Piping Length Farthest Piping Length Farthest Piping Length After First Branch High Low Difference in Indoor Outdoor Section High Low Difference in Indoor Indoor Section Permissible Length Permissible High Low Difference L R H h Selec...

Страница 52: ...nits m and kg Formula When the piping length from the outdoor unit to the farthest indoor unit is 30 5 m 100 ft or shorter Amount of additional charge kg ø19 05 total length 0 29 kg m ø15 88 total length 0 2 kg m ø12 7 total length 0 12 kg m ø9 52 total length 0 06 kg m ø6 35 total length 0 024 kg m Outdoor unit model Amount kg Total capacity of connected indoor units Amount kg P200 0 80 or below ...

Страница 53: ...nt charge Amount of factory charged refrigerant There is a limit to the amount of refrigerant that can be charged into a unit Regardless of the amount yielded by the formula above observe the maximum refrigerant charge in the table below Total index of the outdoor units P200YKB 22 3kg P250YKB 29 7kg P300YKB 32 7kg P350YKB 33 6kg P400YSKB 45 0kg P450YSKB 45 9kg P500YSKB 47 0kg P550YSKB 51 3kg P600Y...

Страница 54: ...lation result to the nearest 0 1kg i e 16 03 kg 16 1 kg Outdoor Twinning kit PURY P YLM Units m and kg In an R2 system Formula When the piping length from the outdoor unit to the farthest indoor unit is 30 5 m 100 ft or shorter Amount of additional charge kg High pressure pipe ø28 58 total length 0 36 kg m High pressure pipe ø22 2 total length 0 23 kg m High pressure pipe ø19 05 total length 0 16 ...

Страница 55: ...gh pressure pipe ø15 88 total length 0 1 kg m Liquid pipe ø15 88 total length 0 18 kg m Liquid pipe ø12 7 total length 0 11 kg m Liquid pipe ø9 52 total length 0 054 kg m Liquid pipe ø6 35 total length 0 021 kg m Total capacity of outdoor units Amount to be added for standard or main BC controller Main BC controller Amount P200 3 0kg HA type 2 0kg P250 4 5kg P300 4 5kg P350 900 6 0kg Number of sub...

Страница 56: ...ON OFF Any time after the power is turned ON Initial settings 2 Mode setting Heating Cooling SW4 SW8 Model Switch 1 6 MODEL SELECTION 1 ON 0 OFF Before the power is turned ON Initial settings Set for each capacity SW5 Function Switch 1 Demand control setting for Demand Responce Mode DRM DRM Existing demand mode Can be set when off or during operation Initial settings Turn ON to activate the demand...

Страница 57: ...educe the performance prevents dew condensation Switching it to raise the performance it raises the power consumption and produces more dew condensation Switching it to reduce the performance it makes the 8 Switching 2 the target evaporation temperature ETm Enable Normal SW7 function switch 1 Ignore current sensor abnormality Enable Normal After turning the power ON Initial settings To perform a t...

Страница 58: ...e rotation speed of the outdoor unit fans CN3D needs to be set Refer to the following page s 2 4 7 Various Control Methods Using the Signal Input Output Connec tor on Outdoor Unit page 28 Switch Function Function according to switch setting Switch setting tim ing Units that require switch setting Note 2 OFF ON SWU 1 2 Unit address setting Set to 00 or 51 100 with the dial switch Before power on C ...

Страница 59: ...l IC Anytime after power on A No 832 0000001011 Cumulative compressor operation time deletion Retained Cleared Anytime after power on OFF ON C No 848 0000101011 Continuous heating cycle function Disabled Enabled After being energized and while the com pressor is stopped A No 896 0000000111 Clearance of error history OC Retained IC OC Deleted IC OC Anytime after power on OFF ON C OS Retained OS Del...

Страница 60: ...t page 25 5 Operation noise is reduced by limiting the frequency of the compressor and rotation speed of the outdoor unit fan Switch Function Function according to switch setting Switch setting timing Units that require switch setting Note 2 OFF ON SWU 1 2 Unit address setting Set to 00 or 51 100 with the dial switch Before power on C SW5 1 Centralized control switch Without connec tion to the cen...

Страница 61: ...utes after compressor start up OFF ON D No 915 1100100111 Defrost start temperature Note 3 EP200 EP350 13 C 9 F EP400 EP500 11 C 12 F 8 C 18 F Anytime after power on B No 916 0010100111 Defrost end temperature Note 3 EP200 EP250 10 C 50 F EP300 EP500 7 C 45 F 5 C 41 F Anytime after power on B No 918 0110100111 Changes the defrost timer setting Note 3 50 minutes 90 minutes Anytime after power on OF...

Страница 62: ...e table below shows the combinations of the settings for items No 964 and No 982 and the target evaporating temperature setting that corresponds to each combination 6 Unless otherwise specified leave the switch to OFF where indicated by which may be set to OFF for a reason 7 The settings that are configured with SW4 SW6 10 ON will automatically be stored on the indoor units that support the new fu...

Страница 63: ...63 DIP SWITCHES INDOOR UNITS ...

Страница 64: ...ts to allow for stratification SW3 1 SW1 7 SW1 8 Change fan speed setting on the indoor unit while in the thermostat OFF position as per the table below This is often used to reduce drafts during the off cycle PLEASE NOTE Some indoor units will come with 8 dip switches on SW3 rather than the 10 shown on the previous page If the unit comes with 8 please note that the dip switches will change as per...

Страница 65: ... will remove this low frequency chatter However it is important to know that this may also reduce the minimum operating capacity of some indoor units causing them to have less accurate temperature control P200 P250 EP250 P300 P350 P400 EP250 EP300 P450 EP350 Cooling Only Cooling Main Heating Only Heating Main Cooling Only Cooling Main Heating Only Heating Main Cooling Only Cooling Main Heating Onl...

Страница 66: ...nd press and hold SWP1 for 2 sec LED3 will become lit to indicate the function is now on Set SW6 10 back to OFF PUMY P V YHMB set SW2 5 to the ON position on the outdoor control board PUMY P VKM set SW9 1 to the ON position on the outdoor control board 3 Auto changeover selected from the central controller with web browser This is only available on central controllers that have a web browser featu...

Страница 67: ...ting 100h 2500h 4 Outside air intake Disabled Enabled 5 Remote display option Fan output Thermo ON signal 6 Humidifier control During heating operation Always on while in the heating mode 7 Fan speed setting for Heating Thermo OFF Very low Low Forced heating operation at OA temp of 5 C or below Not available Available 8 Fan speed setting for Heating Thermo OFF According to the SW1 7 setting Pre se...

Страница 68: ...68 Stanley Street Building Auckland ...

Отзывы: