57
105
The
black
square
(
■
) indicates
a
switch
position.
1
ON
OFF
2 3 4 5 6 7 8
1
ON
OFF
2 3 4 5 6
1
ON
OFF
2
<Initial settings>
Switch Step
Function
Operation in Each Switch Setting
Remarks
Purpose
Additional Information
ON
OFF
When to Set
SW5
function
switch
7
When the outdoor unit is in HEAT
operation, slightly opens the electronic
expansion valve on the indoor unit which
is in FAN, STOP, COOL or thermo-OFF**.
Active
Inactive
Can be set when
OFF or during
operation
To open the LEV opening higher for units other than in
HEAT operation. To avoid a refrigerant shortage (less
capacity) due to refrigerant liquid accumulation in the
units which are not in operation.
A refrigerant
noise might be generated
in units other than the one in operation.
8
When the outdoor unit is in operation,
fully opens the electronic expansion
valve on the indoor unit which is in
FAN, COOL, STOP, or thermo-OFF.***
Enable
Normal
Before turning the
power ON.
To reduce the room temperature increase by setting
the LEV opening lower for the units in thermo-OFF
operation.
The refrigerant is more likely to collect in the units with
thermo-OFF operation, and cause the units refrigerant
shortage. (Results in less capacity and increase of
discharge temperature.)
SW6
function
switch
1
—
—
—
—
<Initial settings>
—
—
2
Switch of current limitation
reading
in a different way
Enable
Normal
Before turning
the power ON.
To lower the primary current limit by 3A.
This switch is used for a single phase model with a
The performance of the unit might be somewhat
limited on this mode.
3
—
—
—
—
—
—
4 Change of defrosting control
Enable
(For high
humidity)
Normal
Can be set
when OFF
or during
operation
To shorten the defrosting prohibition time in high
humidity (or heavy snow) regions, in order to reduce
malfunctions caused by frost .
The performance of the HEAT operation is somewhat
reduced since the defrosting operation is frequently
performed.
5 Ignore refrigerant
abnormality
Enable
Normal
To ignore the error detection of excessive charge of
refrigerant. The unit can be excessively charged with
refrigerant depending on the operating condition.
Make sure that the unit is not excessively charged
with refrigerant before starting operation when
servicing or installing the units.
6 Switching the target discharge
pressure (Pdm)
Enable
Normal
To raise the performance by setting the PDm higher
during HEAT operation.
Power consumption is raised due to a higher
frequency. (The performance would not be raised at the
maximum operating frequency.)
7
Switching (1) the target evaporation
temperature (ETm)
Enable
Normal
To raise/reduce the performance by changing the
target ETm during COOL operation.
Switch to raise the performance: raises the performance
Switch to reduce the performance: prevents dew condensation
Switching it to raise the performance, it raises the power
consumption, and produces more dew condensation.
Switching it to reduce the performance, it makes the
8
Switching (2) the target evaporation
temperature (ETm)
Enable
Normal
SW7
function
switch
1 Ignore current sensor
abnormality
Enable
Normal
After turning
the power ON. <Initial settings>
To perform a test run for electrical parts alone without
running the compressor.
Make sure to connect the connectors to the compressor
after checking the electrical parts.Be careful not to get
an electric shock while working on electrical parts.
2 Setting to energise the freeze
stat heater (optional part)
During
heating
operation
only****
Include when
the heating
operation is
OFF.*****
Can be set when
OFF or during
operation
while the HEAT operation is stopped.
Power consumption raises while the operation is
stopped.
3
—
—
—
—
—
—
4 Maximum frequency down at 1
hour after COOL operation
Enable
Normal
Can be set when
OFF or during
operation
To reduce dew condensation on the indoor unit by
lowering the frequency.
5
—
—
—
—
—
6 Forced defrost
Forced
defrost
Normal
During compressor
running in HEAT
mode.
Turn ON when it is necessary to perform the defrosting
operation forcedly.
(
Effective only at start-up, or 10
minutes after the last defrosting operation)
It performs the defrosting operation forcedly.
(HEAT operation is stopped temporarily.)
SW9
Function
Switch
1 Auto change over from remote
controller
(IC with the minimum address) Enable*
Disable
Before turning the
power ON
<Initial settings>
Enables the indoor unit with the minimum address
to select AUTO mode, and switches the operation
mode of the other indoor units to the same mode.
Cannot be set when the centralized control
is ON.
2 Switching the Silent/ Demand
mode
Demand
control
Silent
mode
Can be set when
OFF or during
operation
—
About the Silent mode/Demand control setting, refer to
"8-6. OUTDOOR UNIT INPUT/OUTPUT CONNECTOR".
When a PWFY series is connected, this function is always disable regardless of the switch.
SW5-7 Opens the indoor-
electronic expansion valve as a countermeasure against the indoor unit in FAN, COOL, STOP, or thermo-OFF operation with refrigerant-shortage status due to an accumulation of liquid refrigerant
in the indoor unit.
SW5-8 Countermeasure against room temperature rise for indoor unit in FAN, COOL, and thermo-OFF (heating) mode.
During heating operation and the ambient temperature is 4
:
(39°F) or below, the freeze prevention heater is energized.
During heating mode is OFF (include thermo-OFF in cooling mode), and the ambient temperature is 4
:
(39°F) or below, the freeze prevention heater is energized.
1
ON
OFF
2 3 4 5 6
SW6-6
OFF ON
Target Pdm (kg/cm²) 29.5 31.5
SW6-7
OFF ON OFF ON
SW6-8
OFF OFF ON
ON
Target ETm (
:
)
9
11
6
14
*
**
***
****
*****
OCH549
to reduce ice build up. Set the base heater to ON
Energises electric heater element within drain tray
PUMY-P-V(Y)KM-A(-BS)
Содержание BDT CITY MULTI
Страница 41: ...41 S SERIES OUTDOOR UNIT WIRING INPUTS AND OUTPUTS CITY MULTI ONLY ...
Страница 42: ...42 INDOOR UNIT WIRING INPUTS AND OUTPUTS CITY MULTI ONLY INPUTS AND OUTPUTS Continued ...
Страница 44: ...44 RECOMMENDED M NET WIRING PROCEDURE CABLE LIMITATIONS AND SYSTEM EXAMPLES ...
Страница 47: ...47 ...
Страница 48: ...48 BASIC SYSTEM M NET WIRING AND ADDRESSING EXAMPLE M NET ADDRESSING Continued ...
Страница 63: ...63 DIP SWITCHES INDOOR UNITS ...
Страница 68: ...68 Stanley Street Building Auckland ...