Appendix On-site adjustment sheet for BAC-HD150 (proposal)
Check these items to use the system.
Group No. [ ]
Control item
Object
Status
Steps
Result
On Off Setup
BO_xxxx01
INACTIVE: Stop
ACTIVE: Run
• Turn ON/OFF the specific group from BMS(*1).
After doing so, check that the operation status of the group
renews the condition using system controller or remote
controller.
On Off State
BI_xxxx02
INACTIVE: Stop
ACTIVE: Run
• Turn ON/OFF the specific group using system controller
or remote controller.
After doing so, check that the operation status of the group
renews the condition on BMS .
Alarm Signal
BI_xxxx03
INACTIVE: Normal
ACTIVE: Error
• Make an error on an air conditioning units of the specific
group.
After doing so, check that the warning signal of the group
turns to (ACTIVE) on BMS. (*2)
• Recover the error of the air conditioning units of the
specific group.
After doing so, check that the warning signal of the group
turns to (INACTIVE) on BMS.
Error Code
MI_xxxx04
01 : Normal
02 : Other errors
03 : Refrigeration fault
04 : Water error
05 : Air error
06 : Electronic error
07 : Sensor fault
08 : Communication error
09 : System error
• Disconnect M-NET transmission line that is connected to
BAC-HD150.
After doing so, check that the error code of all groups turns
to Communication error (08) on BMS. (*3)
• Connect M-NET transmission line to BAC-HD150.
After doing so, check that the error code of all groups turns
to Normal (01) on BMS.
(Do not perform this check when other errors occur.)
Operational Mode
Setup
MO_xxxx05
01 : Cooling
02 : Heating
03 : Fan
04 : Auto
05 : Dry (*4)
06 : Setback
• Change operation mode of the specific group from BMS.
After doing so, check that the operation mode of the group
renews the mode using system controller or remote
controller.
Operational Mode
State
MI_xxxx06
01 : Cooling
02 : Heating
03 : Fan
04 : Auto
05 : Dry (*4)
06 : Setback
• Change operation mode of the specific group using
system controller or remote controller.
After doing so, check that the operation mode of the group
renews the mode on BMS.
Fan Speed Setup
MO_xxxx07
01 : Low
02 : High
03 : Mid 2 (*5)
05 : Mid 1 (*5)
• Change fan speed of the specific group from BMS.
After doing so, check that the fun speed of the group
renews the speed using system controller or remote
controller.
Fan Speed State
MI_xxxx08
01 : Low
02 : High
03 : Mid 2 (*5)
04 : Mid 1 (*5)
• Change fun speed of the specific group using system
controller or remote controller.
After doing so, check that the fun speed of the group
renews the speed on BMS.
Room temp
[Water Temp] (*6)
AI_xxxx09
°F/°C
• Change intake air temperature and check if the display of
BMS and system controller/remote controller are the
same.
Set Temp
[Set Water Temp]
(*6)
AV_xxxx10
°F/°C
• Make a setting of set room temperature of the specific
group from BMS.
After doing so, check that the set room temperature of the
group renews the temperature using system controller or
remote controller.
• Change the set room temperature of the specific group
using system controller or remote controller.
After doing so, check that the set room temperature of the
group renews the temperature on BMS.
Filter Sign
[Circulating Water
Exchange Sign] (*6)
BI_xxxx11
INACTIVE : OFF
ACTIVE : ON
• Perform something to turn on the filter sign. (*2)
After doing so, check that the filter sign of the group turns to
ON(ACTIVE) on BMS.