- 43 -
*1: BMS = Building Management System
*2: Consult a Mitsubishi personnel for the confirmation method.
*3: It can take up to five minutes for an error to be detected.
*4: “Dry” can be used only when “use” is selected for the “Dry” setting (“Dry” is not used for a default.)
*5: “Mid 1/Mid 2” can be used only when “use” is selected for the “Mid 1/Mid 2” setting. (“Mid 1/Mid 2” is not used for a default.)
*6: Inside the brackets indicates control item for BU or AU group. (Refer to section 1.2 Restrictions/Cautions.)
Set Temp Auto
AV_xxxx26
°F/°C
• Make a setting of set room temperature in auto mode of
the specific group from BMS.
After doing so, check that the set room temperature in
auto mode of the group renews the temperature using
system controller or remote controller.
• Change the set room temperature in auto mode of the
specific group using system controller or remote
controller.
After doing so, check that the set room temperature in
auto mode of the group renews the temperature on BMS.
Set High Limit
Setback Temp
AV_xxxx27
°F/°C
• Make a setting of set upper limit temperature in setback
mode of the specific group from BMS.
After doing so, check that the set upper limit temperature
in setback mode of the group renews the temperature
using system controller or remote controller.
• Change the set upper limit temperature in setback mode
of the specific group using system controller or remote
controller.
After doing so, check that the set upper limit temperature
in setback mode of the group renews the temperature on
BMS.
Set Low Limit
Setback Temp
AV_xxxx28
°F/°C
• Make a setting of set lower limit temperature in setback
mode of the specific group from BMS.
After doing so, check that the set lower limit temperature
in setback mode of the group renews the temperature
using system controller or remote controller.
• Change the set lower limit temperature in setback mode of
the specific group using system controller or remote
controller.
After doing so, check that the set lower limit temperature
in setback mode of the group renews the temperature on
BMS.
Ventilation Mode
Setup
MO_xxxx35
01 : Heat exchange
02 : Bypass
03 : Auto
• Change the LOSSNAY ventilation mode of the specific
group from BMS.
After doing so, check that the LOSSNAY ventilation mode of
the group renews the mode using system controller or
remote controller.
Ventilation Mode
State
MI_xxxx36
01 : Heat exchange
02 : Bypass
03 : Auto
• Change the LOSSNAY ventilation mode of the specific
group using system controller or remote controller.
After doing so, check that the LOSSNAY ventilation mode of
the group renews the mode on BMS.
Air To Water Mode
Setup
MO_xxxx37
01 : Heating
02 : Heating ECO
03 : Hot Water
04 : Anti-Freeze
05 : Cooling
• Change the Air To Water mode of the specific group from
BMS.
After doing so, check that the Air To Water mode of the
group renews the mode using system controller or remote
controller.
Air To Water Mode
State
MO_xxxx38
01 : Heating
02 : Heating ECO
03 : Hot Water
04 : Anti-Freeze
05 : Cooling
• Change the Air To Water mode of the specific group using
system controller or remote controller.
After doing so, check that the Air To Water mode of the
group renews the mode on BMS.
Expansion Controller
Communication State
BI_xx9981
INACTIVE : Normal
ACTIVE : Error
• Disconnect the cable that is connected to the BAC-HD150 (LAN
2 port). Confirm that the Expansion Controller communication
status changes to “Error (ACTIVE)” on the BMS.
• Reconnect the cable as it was, and confirm that the
Expansion Controller communication status changes to
“Normal (INACTIVE)” on the BMS.
Control item
Object
Status
Steps
Result