(2) Compatibility of AnS size version Q Series large type base unit with the upgrade tool
The following table shows the compatibility of AnS size version Q Series large type base unit with the upgrade
tool manufactured by Mitsubishi Electric Engineering Co., Ltd. when replacing existing A (Small Type) Series
modules with Q Series modules.
Slot width of base unit
Power supply module
Same width as Q Series base unit
(27.4 mm)
Same width as the A (Large Type)
Series base unit (34.5 mm)
○
○
Item
Base adapter (Upgrade tool)*
2
AnS size version
Q Series large type base unit*
1
Q Series standard power supply module
○
×
Basic model QCPU
CPU module
○
○
×
○
High Performance model QCPU
○
×
Process CPU
○
○
○
○
*
3
Universal model QCPU
Multi-CPU configuration
MELSECNET/H remote I/O module
•
I/O module
•
Intelligent function
module
○
○
*6
Q Series 1-slot module*
4
○
○
×
○
*6
×
Q Series 2-slot occupying module
For terminal block type 16-point I/O module (2-slot type)
For terminal block type 16-point I/O module (1-slot type)
○
*9
○
*6
○
*8
○
*6
○
*8
For high-speed counter module
For analog module (1-slot type)
○
: Applicable (Mountable),
×
: Not Applicable (Not mountable)
Connection of QA/QA1S extension base unit*
7
Conversion
adapter*
5
Mountable
module*
5
○
○
*1: AnS size version Q Series large type base units, Q Series base units (standard products) and Q Series
large base units can be used together.
*2: Mount a Q Series base unit (standard product) on the base adapter manufactured by Mitsubishi Electric
Engineering Co., Ltd.
*3: Q00UJCPU is not compatible.
*4: The following modules cannot be used.
• A module whose height is more than 98 mm.
• A module with a bracket on top.
• A module with a protrusion, such as a connector, on
the bottom.
• A module onto which Q7BAT-SET is mounted.
* Example
Q66AD-DG, Q66DA-G, Q68AD-G, Q68RD3-G, Q68TD-G-H02, Q64AD2DA, QD75M1, QD75MH1,
QD75M2, QD75MH2, QD75M4, QD75MH4, or QJ71WS96 with Q7BAT-SET mounted.
*5: Since the adapters are mounted on Q Series modules, the specifications and functions are same as those
of the Q Series modules. (Please check the transition handbook, since the specifications and functions
are different from those of A (Small type) Series module)
*6: The AnS size version Q Series large type blank cover (QG69LS) must be mounted.
*7: Only High Performance Model QCPUs can be connected to the QA/QA1S extension base unit.
This cannot be used with the MELSECNET/H remote I/O station, etc.
*8: If the size of the copper wire connected to the terminal block is larger than 1.25 mm
2
, it may be difficult to
mount the conversion adapter.
In this case, secure wiring space by leaving empty slots in between modules. For example, mount modules
on slot No. 0, 2, 4, 6, 8, and leave slot No. 1, 3, 5, 7 empty. Mount a blank cover QG60 on the empty slots.
If there are not enough slots, consider using the AnS size version Q Series large type base unit.
*9: Applies when using replacing the existing A (Small Type) module with the two Q Series modules, and using
the existing wiring terminal block with the conversion adapter.
(Example) A1SX20 -> QX28 x 2 modules, A1SY60(E) -> QY68A x 2 modules
MELSEC-AnS Series module
MELSEC-Q Series module
34.5
27.4
Replace with the
terminal block
cover enclosed
with the
conversion
adapter.
• An increase in modules and changes to address can be handled easily by using FA goods.
• A dedicated cable is available to connect the programmable controller with the FA goods, so
there's no need to prepare cables when making a replacement.
Solution and Benefit
Replace
The following is an example of replacing the AnS/QnAS (Small Type) I/O module with the Q Series using FA
goods.
When replacing the AnS/QnAS (Small Type) 200 V AC input module A1SX20 (16-input points, 16-occupied
points), the Q Series 200 V AC input module is QX28 (8-point input, 16-occupied points), so the number of
modules will increase, and the address will change.
By using the FA goods, the modules can be replaced without increasing the number of modules or changing the
address.
●
Instruction
(1) Using the FA goods, convert the 200 V AC input into 24 V DC, and lead it in with QX40.
(2) The external wiring will change, but program does not need to be changed since the I/O address is
the same.
(3) The following FA goods are used.
●
System configuration example
(1) 200 V AC input module insulated with
photo coupler
(2) Input module QX40 on programmable
controller side
(3) Connection cable FA-CBL
TMV20
200 V AC photo
coupler insulated
input module
FA-TH16X200A31L
16-point/common
2-wire type
Product name
Model
External connection
Remarks
Q61PQ01U
CPU
QX40QX40
I/O
module
A1S
61PN
A1S35B
Q35B
FA-CBL06TMV20
FA-CBL06TMV20
A2SH
CPU
A1S
X20
A1S
X20
I/O
module
I/O
module
I/O
module
I/O
module
I/O
module
200 V AC input
FA-TH16X200A31L
FA-TH16X200A31L
Current configuration
New configuration after replacement
2.2.3 Replace AnS/QnAS (Small Type) Series 200 V AC input module A1SX20 without changing I/O
address
52
2.2 Replace AnS/QnAS (Small Type) Series with Q Series
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание Artisan MELSEC-A
Страница 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 25: ...MEMO 22 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 26: ...PartⅠ Hardware 23 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 58: ...MEMO 55 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 90: ...MEMO 87 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 110: ...MEMO 107 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 124: ...MEMO 121 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 131: ...MEMO 128 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 132: ...Part Ⅱ Programming 129 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 160: ...Part Ⅲ Application 157 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 192: ...MEMO 189 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 194: ...MEMO 191 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 195: ...MEMO 192 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...