(CC-Link stackable type)
Power supply module
Product name
CPU module
CC-Link (master module)
Main base unit
Existing module
Replacemant module
A61P
A2NCPU
AJ71PT32-S3
A35B
1
1
Q61P (without 24 V DC)
Q01UCPU
QJ61BT11N
Q35B
1
1
1
1
1
CC-Link input module
AJ35PTF-56DR
AJ65SBTCF1-32D
3
3
CC-Link output module
AJ65SBTCF1-32T
3
1
Interface module
Product name
Programmable controller fixing frame set
Programmable controller connection cable
Mounting plate
Model
Remarks
SC-A0JQIF56DR
SC-A0JQSEL-U1
SC-A0JQC03M
SC-A0JQPT2
For 1-level stackable type
Cable length (0.35 m)
For CC-Link I/O modules
3
3
6
3
Replace
Note: Select appropriate I/O modules according to specifications of existing modules.
A61P
A35B
A2NCPU
I/O module
AJ71PT 32-S3
I/O module
I/O module
I/O module
AJ35PTF-56DR
Terminal block
Terminal
block
AJ35PTF-56DR
Terminal block
AJ35PTF-56DR
Terminal block
SC-A0J
QIF56DR
SC-A0JQSEL-U1
(1-level stackable type)
SC-A0J
QIF56DR
SC-A0JQSEL-U1
(1-level stackable type)
SC-A0J
QIF56DR
SC-A0JQSEL-U1
(1-level stackable type)
Q61P
I/O module
I/O module
Q01U CPU
QJ61BT
11N
I/O module
I/O module
AJ65SBTCF1-32D
AJ65SBTCF1-32T
AJ65SBTCF1-32D
AJ65SBTCF1-32T
AJ65SBTCF1-32D
SC-A0JQPT2
SC-A0JQPT2
SC-A0JQPT2
AJ65SBTCF1-32T
The twisted pair
communication cables
must be replaced with
CC-Link dedicated
cables.
• By mounting existing terminal blocks on the A0J2 upgrade tool (interface module), the compact
type remote I/O modules can be replaced with CC-Link modules without modifying external
wiring.
• Existing compact type remote I/O modules and A0J2 upgrade tools have the same number of I/O
points, realizing the system upgrade without program modification.
* For details on the A0J2 upgrade tool, refer to "Section 2.6 Replace A0J2(H) systems with Q
Series using existing wiring".
Solution and Benefit
The following is an example of replacing MELSECNET/MINI compact type remote I/O modules with CC-Link
using the A0J2 upgrade tool.
●
Instructions
(1) Select connector type CC-Link I/O modules to allow connection with the A0J2 upgrade tools.
(2) Select a CC-Link I/O module for replacement with a connector type external wiring to enable use of the
A0J2 upgrade tool connection dedicated cable.
(1) System configuration example
●
Module selection example
(1) Programmable controller
(2) A0J2 upgrade tool
Current configuration
New configuration after replacement
Existing terminal block
Existing terminal block
Existing terminal block
Existing terminal block
Existing terminal block
Existing terminal block
Existing terminal block
Existing terminal block
Existing terminal block
Existing terminal block
Existing terminal block
Existing terminal block
• MELSECNET/MINI twisted pair cables must be replaced with CC-Link dedicated cables.
• CC
-Link I/O modules and A0J2 upgrade tools (interface modules) require 24 V DC power supply in addition
to power supply for control. Prepare a 24 V DC power supply separately.
• W
hen using the stackable type renewal tool as shown in the example, make sure there is enough depth.
(Required depth: 120 mm or more)
The mounting plate for CC-Link I/O modules is sold separately.
• Also the CPU can be replaced with LCPU.
When it is replaced with L Series, the CC-Link master module LJ61BT11 or the built-in CC-Link function of
the CPU will be used.
The remote module is common to Q Series and L Series.
Tip
2.4.3 Replace MELSECNET/MINI compact type remote I/O modules with CC-Link
71
2.4 Replace A0J2 with Q Series
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание Artisan MELSEC-A
Страница 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 25: ...MEMO 22 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 26: ...PartⅠ Hardware 23 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 58: ...MEMO 55 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 90: ...MEMO 87 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 110: ...MEMO 107 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 124: ...MEMO 121 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 131: ...MEMO 128 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 132: ...Part Ⅱ Programming 129 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 160: ...Part Ⅲ Application 157 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 192: ...MEMO 189 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 194: ...MEMO 191 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 195: ...MEMO 192 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...