4 SYSTEM CONFIGURATION
4.5 Rules of System Configuration and Examples of Reconfiguration
71
4
Check of limitation on the number of input/output points
Check if the number of input/output points of the sample system configuration is within the limit range.
■
Number of input/output points
(
Page 56 Calculation of number of input/output points)
■
Number of remote I/O points
(
Page 57 Calculation of number of remote I/O points)
■
Total number of I/O points and remote I/O points
(
Page 55 Limitation on the Number of Input/Output Points)
Type
Model
No. of input/output
points
No. of occupied input/
output points
CPU module
FX5U-32MR/ES
32 points
Expansion board
FX5-232-BD
Expansion adapter
FX5-232ADP
Expansion adapter
FX5-485ADP
Input module
FX5-16EX/ES
16 points
Output module
FX5-16EYT/ES
16 points
Output module
FX5-16EYT/ES
16 points
Output module
FX5-16EYR/ES
16 points
Simple motion module
FX5-40SSC-S
8 points
Bus conversion module
FX5-CNV-BUS
8 points
Pulse output module
FX3U-1PG
8 points
Analog input module
FX3U-4AD
8 points
Temperature controller module
FX3U-4LC
8 points
AnyWireASLINK master module
FX3U-128ASL-M
8 points
CC-Link intelligent device module
FX3U-64CCL
8 points
Network
No. of remote I/O points
AnyWireASLINK
64 points
+
96 points
≤
56 points
256 points
Number of input/output points
152 points
Calculation result
=
OK
Number of
input/output points
Number of occupied
input/output points
Max. number of
input/output points
≤
384 points
Remote I/O points
64 points
OK
Maximum number of
Remote I/O points
≤
152 points
512 points
Number of input/output points
+
Remote I/O points
64 points
Total number of input/output points
= 216 points
OK
Max. number of
input/output points
Calculation
result