6 WIRING
6.5 Input Wiring
111
6
■
Input circuit
■
Input sensitivity
■
Display of operation
The LED turns ON when the photocoupler is driven.
With FX5-C32EX/
or FX5-C32ET/
, the LED target is switched with the DISP switch.
• FX5-C32EX/
: Smaller number (F)/Larger number (L)
• FX5-C32ET/
: Input (IN)/Output (OUT)
• Function of input circuit
The primary and secondary circuits for input are insulated with a photocoupler, and the second circuit is provided with a C-R filter.
The C-R filter is designed to prevent malfunctions caused by chattering of the input contact and noise from the input line.
Input has a response delay switching from ON to OFF and OFF to ON, shown in the following table.
Item
Specifications
Input response time
(H/W filter delay)
FX5U-32M
X0 to X5
ON: 2.5
μ
s or less
OFF: 2.5
μ
s or less
FX5U-64M
, FX5U-80M
X0 to X7
High-speed pulse input/output module
X0 to X5
FX5U-32M
X6 to X17
ON: 30
μ
s or less
OFF: 50
μ
s or less
FX5U-64M
, FX5U-80M
X10 to X17
High-speed pulse input/output module
X6, X7
FX5U-64M
, FX5U-80M
X20 and
subsequent
ON: 50
μ
s or less
OFF: 150
μ
s or less
Input module, Input/output modules, Powered input/
output module
• Change of filter time
All input circuits have digital filters, and the input response time shown in the following table can be added by setting parameters.
When using this product in an environment with much noise, set the digital filter.
Item
Specifications
Input response time
(Digital filter setting value)
None, 10
μ
s, 50
μ
s, 0.1 ms, 0.2 ms, 0.4 ms, 0.6 ms, 1 ms, 5 ms, 10 ms (initial values), 20 ms, 70 ms
For input signal current and Input sensitivity current of the CPU module, refer to
For input signal current and Input sensitivity current of the I/O modules, refer to
Содержание 09R536