26
2 SPECIFICATIONS
2.4 Output Specifications
2.4
Output Specifications
The CPU module output specifications are explained below.
Relay output
Item
Output Specifications
No. of output points
FX5U-32MR/
16 points
FX5U-64MR/
32 points
FX5U-80MR/
40 points
Connection type
Removable terminal block (M3 screws)
Output type
Relay
External power supply
30 V DC or less
240 V AC or less ("250 V AC or less" if not a CE, UL, cUL compliant item)
Max. load
2 A/point
The total load current per common terminal should be the following value.
• 4 output points/common terminal: 8 A or less
• 8 output points/common terminal: 8 A or less
For details on the common, refer to
Page 35 Interpretation of terminal block layout.
Min. load
5 V DC, 2 mA (reference values)
Open circuit leakage current
Response time
OFF
→
ON
Approx. 10 ms
ON
→
OFF
Approx. 10 ms
Insulation of circuit
Mechanical insulation
Indication of output operation
LED is lit when output is on
Output circuit configuration
A number is entered in the of [COM ].
AC power supply
Load
Fuse
Y
DC power supply
Fuse
Y
COM
COM
Load