APPX
Appendix 5 I/O Module
181
A
Output specifications
There is the simultaneous ON ratio of available PLC inputs or outputs with respect to the ambient temperature.
For details, refer to
Page 27 Input/Output Derating Curve
■
Relay output
■
Transistor output (sink output)
Item
Specifications
No. of output points
FX5-8EYR/ES
8 points
FX5-16EYR/ES
16 points
FX5-16ER/ES
8 points
FX5-32ER/
S
16 points
Connection type
Terminal block (M3 screws)
Output type
Relay
External power supply
30 V DC or less
240 V AC or less
(250 V AC or less when the module does not comply with CE UL, cUL standards)
Output circuit insulation
Mechanical insulation
Indication of output operation
LED is lit when output is on
Max. load
2 A/point
The total load current of resistance loads per common terminal should be the following value.
• 4 output points/common terminal: 8 A or less
• 8 output points/common terminal: 8 A or less
Open circuit leakage current
Min. load
5 V DC, 2 mA (reference values)
Response time
OFF
→
ON
Approx. 10 ms
ON
→
OFF
Approx. 10 ms
Output circuit configuration
Item
Specifications
No. of output points
FX5-8EYT/ES
8 points
FX5-16EYT/ES
16 points
FX5-16ET/ES
8 points
FX5-32ET/
S
16 points
FX5-16ET/ES-H
8 points
FX5-C16EYT/D
16 points
FX5-C32EYT/D
32 points
FX5-C32ET/D
16 points
Connection type
FX5-
EYT/ES,
FX5-16ET/ES,
FX5-32ET/
S,
FX5-16ET/ES-H
Terminal block (M3 screws)
FX5-C
EYT/D,
FX5-C32ET/D
Connector
Output type
Transistor/sink output
External power supply
5 to 30 V DC
Output circuit insulation
Photo-coupler insulation
Indication of output operation
LED is lit when output is on
• With FX5-C32EYT/
, the lower number/higher number order is switched with the DISP switch F/L.
• With FX5-C32ET/
, the input/output is switched with the DISP switch IN/OUT.
Load
Fuse
Fuse
Y
COM0
Y
COM1
AC power
supply
DC power
supply
Содержание 09R536