4 SYSTEM CONFIGURATION
4.3 Limitation on the Number of Input/Output Points
Total number of I/O points and remote I/O points
With the FX5U CPU module, a total of 512 points or less including the number of input/output points of extension devices and
number of remote I/O points can be controlled.
The total number of I/O points and remote I/O points must not exceed 512 points.
Calculation of number of input/output points
The number of input/output points is the total of the number of input/output points of the CPU module and I/O module, and the
number of occupied input/output points of intelligent function modules.
The total number of input/output points must not exceed 256 points.
Total number of input/output points of the CPU module and I/O modules
Count the total number of input/output points of the CPU module and I/O modules.
To obtain the total number of input/output points, count the input points (X0 and more) and output points (Y0 and more) of the
CPU module and I/O modules.
For details on the number of input/output points by model, refer to the following.
Number of occupied input/output points of intelligent function modules
Count the number of occupied input/output points of intelligent function modules.
The number of occupied input/output points per module is 8.
For details on the number of occupied input/output points by model, refer to
Page 43 Intelligent Function Module.
≥
512 points
+
Number of remote I/O points
(2)
points
Number of input/output points
(1)
points
Maximum number of
points controllable on
system
The total number of inputs and
outputs which is obtained in the
next subsection.
The total number of remote I/O
which is obtained in the next
subsection.
Number of input/output
points on whole system
≥
256 points
+
(A)
+
(B)
(C) modules ×8 points
=
(1)
Total number of input/output points of CPU
module and I/O modules
(A): Number of input/output points of CPU module
(B): Number of input/output points of I/O modules
(C): Number of Intelligent function modules and bus conversion modules
Intelligent function module,
bus conversion module
occupies 8 input/output points.
Maximum number of
input/output points
Number of
input/output points
Number of input/output points on
CPU module and I/O module
Number of input/output
occupied points