20
Install the heatsink
After the socket is fully actuated from procedures in Fig 25 to 27 (component on left), the heatsink
(bottom side shown
–
component on right) can then be installed on top of the CPU Package lid by
securing the four captive screws on the heatsink base to the four PEM nuts on the Stiffener Frame
(shown in red circles above).
The screw and PEM nuts are located asymmetrically so that the heatsink can be installed in the correct
orientation only. The heatsink uses the same Torx T20 head screws as the Socket Actuation
Mechanism.
Содержание E8020
Страница 1: ...E8020 OCP Computing Sled User Manual Version 1 0 ...
Страница 7: ...2 APPENDIX A 124 ...
Страница 12: ...7 2 1 2 Ultra Note 4x U 2 drives One FHHL PCIe card ...
Страница 29: ...24 2 2 5 Release the Drive A Pull the locking Drive lever open in the direction of arrow B Take out Drive ...
Страница 32: ...27 B Push the Right Left handle bar to lock the Drive Cage ...
Страница 33: ...28 C Insert the Riser Card ...
Страница 34: ...29 D Fasten the latch to lock the riser card E Open the retainer as shown ...
Страница 36: ...31 3 Mainboard Information 3 1 Board Introduction Here are different views of the main board ...
Страница 39: ...34 3 4 Block Diagram ...
Страница 47: ...42 CPU 0 Information ...
Страница 50: ...45 4 3 4 Serial Port Console Redirection ...
Страница 54: ...49 Console Redirection Settings COM1 ...
Страница 62: ...57 4 3 7 USB Configuration ...
Страница 73: ...68 Socket 0 Information View Information related to Socket 0 ...
Страница 94: ...89 4 9 Save Exit ...
Страница 127: ...122 Here is the example of OOB BIOS update IP Your BMC IP C439_TGPSNTT_101 BIN The BMC image you received ...
Страница 128: ...123 6 2 2 BMC update You can do BMC update via local or OOB Example of local BMC update Example of BMC update via OOB ...