Configuration with the CFG-300 LCD Service Tool
11.11.5 Auto Test Time and Cellular Report Date
If the Cellular report date is set to 0, then the dialer alternates between Lines 1 and 2 when
performing the automatic test. If the Cellular report date is not set to 0, then the automatic test
is performed on Line 1 except on the Cellular report date, when it is performed on Line 2. See
examples in the following table.
11.11.6 Command Menu/Dialer Config-->Dialer Enable/Disable
Cellular Report Date
Auto Test Time
Line 1 Tested
Line 2 Tested
0
00:30
12:30 a.m. every other day
(alternates with Line 2)
12:30 a.m. every other day
(alternates with Line 1)
0
6:00
6:00 a.m. and 6:00 p.m.
12:00 p.m. and 12:00 a.m.
0
12:00
12:00 p.m.
12:00 a.m.
15
00:30
12:30 a.m. every day
except on the 15th of the
month
12:30 a.m. on the 15th of
the month
15
6:00
6:00 a.m., 12:00 p.m., 6:00
p.m., and 12:00 a.m. every
day except on the 15th of
the month
6:00 a.m., 12:00 p.m., 6:00
p.m., and 12:00 a.m. on
the 15th of the month
15
12:00
12:00 p.m. and 12:00 a.m.
every day except on the
15th of the month
12:00 p.m. and 12:00 a.m.
on the 15th of the month
Note:
Refer to 11.2.1 Using the Keypad to Program the FA-300 on page 61 for detailed
instructions on making menu selections.
[X] ENABLE ->Default
[ ] DISABLE
The dialer is enabled by
default. When the dialer is
enabled or disabled, a
warning message appears.
Warning:
The
dialer cannot
report any event to the
monitoring station if it is
disabled.
i
D i a l e r E n a / D i s
[ X ] E N A B L E
- - - - - - W a r n i n g - - - - - - -
D i a l e r D i s a b l e d ! ! !